234# Generator Control
No. Name
01
GnVtgMin
02
GnVtgMax
03
GnCurNom
04
GnFrqNom
05
GnFrqMin
06
GnFrqMax
07
GnStrMod
08
GnOpTmMin
09
GnStpTmMin
10
GnCoolTm
11
GnErrStpTm
12
GnWarmTm
13
GnRvPwr
14
GnRvTm
15
GnCtlMod
Operating Manual
Description
Minimum generator
voltage
Maximum generator
voltage
Nominal generator
current
Nominal generator
frequency at nominal
load
Minimum generator
frequency
Maximum generator
frequency
Generator interface
Minimum run time of
the generator
Minimum stop time of
the generator
Cooling time of the
generator
Stop time of generator
in case of errors
Warm-up time
Generator reverse
power (active power)
Permissible time for
reverse power/reverse
current
Generator regulation
Value
Explanation
Manual
Manual
Autostart
Automatic
GenMan
SMA generator
management box
Cur
Current
CurFrq
Frequency
SI4548-6048-US-BE-en-21
19  Parameter Lists
Default
value
80 V
150 V
30 A
60 Hz
54 Hz
66 Hz
Autostart
15 min
15 min
5 min
1 h
60 sec
100 W
30 sec
Cur