SMA SUNNY ISLAND 4548-US Operating Manual page 169

Off-grid inverter
Hide thumbs Also See for SUNNY ISLAND 4548-US:
Table of Contents

Advertisement

SMA Solar Technology America LLC
#222 Battery Charge Mode
No. Name
01
BatChrgCurMax Charging current
02
AptTmBoost
03
AptTmFul
04
AptTmEqu
05
CycTmFul
06
CycTmEqu
07
ChrgVtgBoost
08
ChrgVtgFul
09
ChrgVtgEqu
10
ChrgVtgFlo
Operating Manual
Description
Value
10 A to 1,200 A
of the battery
Absorption time for
1 min to 600 min
normal charge
1 min to 600 min
1 min to 600 min
Absorption time for
1 h to 20 h
full charge
1 h to 20 h
1 h to 20 h
Absorption time for
1 h to 48 h
equalization
charge
Cycle time of full
1 day to 180 days
charge
Equalization
7 days to 365
charge cycle time
days
Cell voltage
2.2 V to 2.7 V
setpoint for normal
charge
1.5 V to 1.8 V
Cell voltage
2.3 V to 2.7 V
setpoint for full
charge
1.5 V to 1.8 V
Cell voltage
2.3 V to 2.7 V
setpoint for
equalization
1.5 V to 1.8 V
charge
Cell voltage
2.2 V to 2.4 V
setpoint for float
charge
1.4 V to 1.6 V
19  Parameter Lists
Explanation
VRLA
FLA
NiCd
VRLA
FLA
NiCd
VRLA
FLA
NiCd
VRLA
FLA
NiCd
VRLA
FLA
NiCd
VRLA
FLA
NiCd
SI4548-6048-US-BE-en-21
Default
value
61 A
120 min
90 min
300 min
5 h
5 h
7 h
10 h
14 days
180
days
2.40 V
2.55 V
1.65 V
2.40 V
2.50 V
1.65 V
2.40 V
2.50 V
1.65 V
2.25 V
2.25 V
1.55 V
169

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Sunny island 6048-usSunny island 4548-us-10

Table of Contents