NTI ENVIROMUX TEMPERATURE/HUMIDITY SENSOR ATTACHMENT
TEMPERATURE AND HUMIDITY SENSORS
SENSOR MODEL
ENVIROMUX-STS
ENVIROMUX-SHS
ENVIROMUX-STSM-E7
ENVIROMUX-STHS-99
ENVIROMUX-STHS-N4085IND
ENVIROMUX-STHS-
N4085IND-O
ENVIROMUX-STHSB /
ENVIRMUX-STHSM-E7
ENVIROMUX-STHS-LCD
ENVIROMUX-STHS-PRC
ENVIROMUX-STHS-PRCIND
ENVIROMUX-STHS-
PRCIND100-Pxx
ENVIROMUX-STHS-WLM
ENVIROMUX-STSP
ENVIROMUX-STSP-SL-7
ENVIROMUX-STS-PRC

Sensor Calibration

All temperature/humidity combination sensors and humidity-only sensors are factory-calibrated and are not designed to be
calibrated in the field. In the event recalibration of your sensor is desired, please contact NTI for an RMA to return your sensor.
Sensors within warranty will be recalibrated at no charge. Normal labor charges will apply to sensors out of warranty.
OPERATING TEMPERATURE
RANGE
32 to 122°F (0 to 50°C)
n/a
-4 to 185°F (-20 to 85°C)
32 to 176°F (0 to 80°C)
-40°F to 185°F (-40°C to +85°C)
Accurate at -4°F to 185°F
(-20°C to +85°C)
-40°F to 185°F (-40°C to +85°C)
Accurate at -4°F to 185°F
(-20°C to +85°C)
-4 to 185°F (-20 to 85°C)
-4 to 140°F (-20 to 60°C)
32 to 140°F (0 to 60°C)
-40 to 185°F (-40 to 85°C)
-40 to 212°F (-40 to 100°C)
23 to 131°F (-5 to 55°C)
-40 to 185°F (-40 to 85°C)
32 to 140°F (0 to 60°C)
HUMIDITY RANGE
n/a
20 to 80% RH.
n/a
20 to 80% RH, ±3%
10 to 90% RH, ±4%
• 0 to 99% RH, ±5%
± 5% from 20% to 80%
RH(measured at 25°C)
± 5% from 20% to 80%
RH(measured at 25°C)
0 to 90% RH
0 to 90% RH
10% to 80% RH
10% to 80% RH
10% to 80% RH
10 to 90% RH
n/a
n/a
6
ACCURACY
±0.9°F (±0.5°C)
±5% RH
±1.26°F (±0.70°C) for -4
to 41°F (-20 to 5°C)
±0.72°F (±0.40°C) for 41
to 140°F (5 to 60°C)
±2°F (0 to 50°C, ±1°C)
±0.9°F (±0.5°C). and
±5% RH@ 77°F (25°C)
±0.9°F (±0.5°C). and
±5% RH@ 77°F (25°C)
±0.7°F (±0.4°C).
±4% RH (30°C)
±0.7°F (±0.4°C).
±4% RH (30°C)
± 0.4°F(±0.2°C)
± 1.8%RH@86°F (30°C)
± 0.4°F(±0.2°C)
± 1.8%RH@86°F (30°C)
± 0.4°F(±0.2°C)
± 1.8%RH@86°F (30°C)
±0.54°F (±0.3°C). and
±3% RH@68°F (20°C)
±1.0°F (±0.5°C).
±0.2°F (±0.1°C).