Introduction EDMT331529A 1. Introduction Publication List of Engineering Data for VRV Products Published Refrigerant Type Product Series Book No. Type, Hz Model name Area Note High-COP type Argentina, (Energy Saving Type) Chile, RXYQ12-50THY1(E) Uruguay - Revision for and other EU Biocidal EDMT341421A H/P 50 Hz Standard type...
EDMT331529A Part 1 General Information 1. Model Names of Indoor/Outdoor Units............4 1.1 Indoor Units ....................4 1.2 Outdoor Units ...................5 1.3 Air Treatment Equipment .................5 2. External Appearance................6 2.1 Indoor Units ....................6 2.2 Outdoor Units ...................8 2.3 Air Treatment Equipment .................8 3.
Model Names of Indoor/Outdoor Units EDMT331529A 1. Model Names of Indoor/Outdoor Units Indoor Units VRV Indoor Units 2.2kW 2.8kW 3.6kW 4.5kW 5.6kW 7.1kW 8.0kW 9.0kW 11.2kW 14.0kW 16.0kW 22.4kW 28.0kW Power Capacity range 0.8HP 1.25HP 1.6HP 2.5HP 3.2HP 10HP supply, Standard Capacity index 31.25...
EDMT331529A Model Names of Indoor/Outdoor Units Residential Indoor Units with Connection to BP Units Heat Pump Capacity range 2.0kW 2.5kW 3.5kW 5.0kW 6.0kW 7.1kW Power supply, Capacity index Standard CDXS — 25EA 35EA — — — Slim Ceiling Mounted Duct Type FDXS —...
External Appearance EDMT331529A 2. External Appearance Indoor Units VRV Indoor Units Ceiling mounted cassette (Round flow with sensing) type Ceiling mounted duct type FXFQ-S FXMQ-P Ceiling mounted cassette (Round flow) type Ceiling mounted duct type FXFQ-LU FXMQ-MA Ceiling mounted cassette (Compact multi flow) type Ceiling suspended type FXZQ-M FXHQ-MA...
Page 9
EDMT331529A External Appearance Residential Indoor Units with Connection to BP Units Slim ceiling mounted duct type Wall mounted type (700 mm width type) FTXS-D CDXS-EA FTXS-E Slim ceiling mounted duct type Wall mounted type (900/1,100 mm width type) FTXS-F FDXS-C Wall mounted type FTXJ-N BP Units...
Page 12
Nomenclature EDMT331529A Residential Indoor Unit (SPLIT) Front panel colour symbol Suffixed when the model has colour variations W: White S: Silver Standard symbol A: Australia Power supply symbol VM: 1 phase, 220-240/220-230V, 50/60 Hz V1: 1 phase, 220-240V, 50 Hz Model change symbol Progress with each design change Capacity indication...
Page 13
EDMT331529A Nomenclature Outdoor Unit Power supply symbol VE: 1 phase, 220-230/220V, 50/60Hz Y1: 3 phase, 380-415V, 50Hz Indicates major design category Capacity indication Conversion to kW (Horsepower) 4: 11.2 kW (4 HP) 6: 16.0 kW (6 HP) 9: 24.0 kW (9 HP) Refrigerant Q: R410A Shape...
Capacity Range EDMT331529A 4. Capacity Range Capacity Range for VRV Indoor Units Only 4.1.1 Combination Ratio Total capacity index of the indoor units Combination ratio = Capacity index of the outdoor units Max. combination ratio Type Min. combination ratio Types of connected indoor units VRV indoor units Single outdoor units 130%...
EDMT331529A Capacity Range Capacity Range for Mixed Combination of VRV and Residential Indoor Units 4.2.1 Combination Ratio Total capacity index of the indoor units Combination ratio = Capacity index of the outdoor units Max. combination ratio Type Min. combination ratio Type of connected indoor units VRV and Residential indoor units *1 Single outdoor units...
Selection Procedure EDMT331529A 5. Selection Procedure Selection Procedure for VRV Indoor Units Only 5.1.1 Flowchart Given Conditions: · Design temperature and humidity (indoor & outdoor) [1] ] Given conditions · Required heat load of each room · System peak load ( if necessary) ·...
Page 17
EDMT331529A Selection Procedure Equivalent pipe length 30m Level difference Select VRV indoor units FXMQ-P series for each room. -Safety factor In this example, safety factor is not used. (i. e., safety factor = 1.0) [2] Selection of indoor units Calculate total heat capacity of indoor units corrected for indoor air temperature. In case design temperature of the indoor air falls between temperatures listed in the table, calculate the capacity by interpolation.
Page 18
Selection Procedure EDMT331529A [3] –2 Provisionally select outdoor unit (1) Calculate CI (Capacity Index) of the selected indoor units. CI of VRV indoor units VRV Indoor Units CI of FXMQ20PVE = 20 2.2kW 2.8kW 3.6kW 4.5kW 5.6kW 7.1kW 8.0kW 9.0kW 11.2kW 14.0kW 16.0kW 22.4kW 28.0kW Power Capacity range CI of FXMQ32PVE = 31.25...
Page 19
EDMT331529A Selection Procedure -Confirm capacity correction factor by piping length and level difference (K1) (K1) = 0.95 0.95 -Calculate capacity correction factor by piping heat loss (K2) (K2) = 1 + (heat loss factor per meter of piping × (equivalent piping length – 7.5m)) / 100 In cooling mode, heat loss factor per meter at 33°C is calculated as below.
Selection Procedure EDMT331529A Selection Procedure for Mixed Selection of VRV and Residential Indoor Units 5.2.1 Flowchart For the selection of residential indoor units, the following procedures shall be added to the standard selection of VRV indoor units. -Correct the capacity of VRV indoor units for “Evaporating temperature (Te: 9ºC)”. (only for cooling capacity) -Correct the capacity of Residential indoor units for “Indoor air temperature”.
Page 22
Selection Procedure EDMT331529A [3] –2 Provisionally select outdoor unit (1) Calculate CI (Capacity Index) of the selected indoor units. CI of VRV indoor units VRV Indoor Units 2.2kW 2.8kW 3.6kW 4.5kW 5.6kW 7.1kW 8.0kW 9.0kW 11.2kW 14.0kW 16.0kW 22.4kW 28.0kW CI of FXDQ20PBVE = 20 Power Capacity range...
Page 23
EDMT331529A Selection Procedure [3] –3 Calculate the corrected capacity of the outdoor unit. Using the capacity table of the outdoor unit, calculate the capacity (B) corrected for “Outdoor air temperature”, “Indoor air temperature”, “Combination ratio”, and “Correction factor for outdoor units”. RXYMQ8AY1 Cooling capacity (Capacity correction factor: 0.95) (Te: 9ºC) RXYMQ8AY1 Cooling capacity (Capacity correction factor: 0.90) (Te: 9ºC) -Calculate the capacity in case combination ratio = 104%...
Page 24
Selection Procedure EDMT331529A -Confirm capacity correction factor for piping length and level difference (K1) (K1) = 0.95 0.95 -Calculate capacity correction factor for piping heat loss (K2) (K2) = 1 + (heat loss factor per meter of piping × (equivalent piping length – 7.5m)) / 100 Heat loss factor per meter at 33ºC is calculated as below.
EDMT331529A Part 2 Indoor Units FXFQ-S Ceiling Mounted Cassette (Round Flow with Sensing) Type ... . . 25 FXFQ-LU Ceiling Mounted Cassette (Round Flow) Type ......43 FXZQ-M Ceiling Mounted Cassette (Compact Multi Flow) Type .
Page 26
EDMT331529A FXLQ-MA / FXNQ-MA Floor Standing Type / Concealed Floor Standing Type ... . . 243 FXVQ-N Floor Standing Duct Type ....269 Indoor Units...
EDMT331529A Air Velocity and Temperature Distributions (Reference Data) 8. Air Velocity and Temperature Distributions (Reference Data) FXZQ20MVE / FXZQ25MVE (Cooling) 4D039738D FXZQ20MVE / FXZQ25MVE (Heating) 4D039820D FXZQ-M...
Page 74
Air Velocity and Temperature Distributions (Reference Data) EDMT331529A FXZQ32MVE (Cooling) 4D040188A FXZQ32MVE (Heating) 4D040191A FXZQ-M...
Page 75
EDMT331529A Air Velocity and Temperature Distributions (Reference Data) FXZQ40MVE (Cooling) 4D040189A FXZQ40MVE (Heating) 4D040192A FXZQ-M...
Page 76
Air Velocity and Temperature Distributions (Reference Data) EDMT331529A FXZQ50MVE (Cooling) 4D040190A FXZQ50MVE (Heating) 4D040193A FXZQ-M...
EDMT331529A Safety Devices Setting 6. Safety Devices Setting Model FXUQ71AVEB FXUQ100AVEB Fuse 250V 3.15A 250V 3.15A Fan motor thermal fuse °C – – Fan motor thermal protector °C – – 4D013856M FXUQ-A...
EDMT331529A Air Velocity and Temperature Distributions (Reference Data) 8. Air Velocity and Temperature Distributions (Reference Data) FXCQ63MVE (Heating · Air velocity distribution) Discharge angle : 60° FXCQ63MVE (Heating · Temperature distribution) Discharge angle : 60° Note: The standard setup height of the double flow type is 3 m maximum. Shown here is the measurement distribution at the ceiling height of 3 m.
Page 110
Air Velocity and Temperature Distributions (Reference Data) EDMT331529A FXCQ125MVE (Heating · Air velocity distribution) Discharge angle : 60° FXCQ125MVE (Heating · Temperature distribution) Discharge angle : 60° Note: The standard setup height of the double flow type is 3 m maximum. Shown here is the measurement distribution at the ceiling height of 3 m.
EDMT331529A Air Velocity and Temperature Distributions (Reference Data) 8. Air Velocity and Temperature Distributions (Reference Data) FXKQ63MAVE (Heating · Air velocity distribution) Lower airflow FXKQ63MAVE (Heating · Temperature distribution) Lower airflow Note: The corner type is applicable on a high ceiling. The standard setup height is 3 m. Shown here is the measurement distribution at the ceiling height of 3 m.
EDMT331529A Fan Performances 8. Fan Performances FXDQ-PB FXDQ20PBVE / FXDQ25PBVE FXDQ32PBVE FXDQ20PBVET / FXDQ25PBVET FXDQ32PBVET C: 3D052156D C: 3D052157D Notes: 1. The remote controller can be used to switch between “HH”, “H” and “L”. 2. The airflow is set to “standard” before leaving the factory. It is possible to switch between “standard ESP”...
Fan Performances EDMT331529A FXDQ-NB FXDQ40NBVE FXDQ50NBVE FXDQ40NBVET FXDQ50NBVET C: 3D046299F C: 3D046300F FXDQ63NBVE FXDQ63NBVET C: 3D046301F Notes: 1. The remote controller can be used to switch between “HH”, “H” and “L”. 2. The airflow is set to “standard” before leaving the factory. It is possible to switch between “standard ESP”...
Air Velocity and Temperature Distributions (Reference Data) EDMT331529A 8. Air Velocity and Temperature Distributions (Reference Data) FXHQ100MAVE (Heating · Air velocity distribution) Centre airflow FXHQ100MAVE (Heating · Temperature distribution) Centre airflow FXHQ-MA...
Fan Characteristics (For Pulley Selection) EDMT331529A Fan Motor Specifications Rated motor output 0.75 Items φS 1. Shaft outer diameter 2. Shaft length Motor 3. Keyway width 4. Keyway depth 5. Insulation class φd 1. Shaft hole diameter Type A and V Pulley 2.
Takes 3 belts Pulley outer diameter At Daikin, the outer diameter is used in pulley sizes. Pitch Diameter (the actual diameter of the parts in contact with the belt) The pulley makers often use the pitch diameter in pulley sizes.
Page 290
Fan Characteristics (For Pulley Selection) EDMT331529A Tension of V belt • Tension of a V belt must meet the deflection load (W) as shown. Calculate the required deflection length (L) by the equation (1), its tolerance must be within the range as below. Deflection load L= 0.016 ×...
EDMT331529A Fan Characteristics (For Pulley Selection) V Belt Size Table Refer to the JIS K 6323 (V belt) for details. (JIS: Japanese Industrial Standards) (Unit: mm) Nominal Nominal Nominal Nominal Type A Type B Type A Type B Type A Type B Type A Type B...
Dimensions of Optional Accessories EDMT331529A 13. Dimensions of Optional Accessories FXVQ125NY1 Unit (mm) 3D083638B FXVQ200NY1 Unit (mm) 3D083639B FXVQ-N...
Page 297
EDMT331529A Dimensions of Optional Accessories FXVQ250NY1 Unit (mm) 3D083640B FXVQ-N...
Data and Notice in Using the Outdoor-Air Processing Mode EDMT331529A 14. Data and Notice in Using the Outdoor-Air Processing Mode The FXVQ-series can be modified to the following operation mode. - Outdoor air processing mode It supports cooling and heating operations by introducing outdoor air. In this outdoor-air processing mode, you cannot control the room temperature.
Page 299
EDMT331529A Data and Notice in Using the Outdoor-Air Processing Mode Field settings [In case of VRV IV] Be sure to set from both (a) Field settings from the indoor unit and (b) Field settings from the outdoor unit. (a) Field settings from the indoor unit You need to configure the settings by the control panel of the indoor unit to change the operation mode.
Page 300
Data and Notice in Using the Outdoor-Air Processing Mode EDMT331529A Specification table (outdoor-air processing mode) Model name FXVQ125NY1 FXVQ200NY1 FXVQ250NY1 Cooling capacity 16.8 26.8 33.5 Heating capacity 14.0 22.4 28.0 Airflow rate /min External static pressure ...
EDMT331529A Part 3 Residential Indoor Units with Connection to BP Units Heat Pump <SPLIT> CDXS25EAVMA FTXJ25NVMVW CDXS35EAVMA FTXJ25NVMVS FDXS25CVMA FTXJ35NVMVW FDXS35CVMA FTXJ35NVMVS FDXS50CVMA FTXJ50NVMVW FDXS60CVMA FTXJ50NVMVS FTXS20DVMA FTXS25EVMA FTXS35EVMA FTXS50FVMA FTXS60FVMA FTXS71FVMA 1. Power Supply ..................301 2. Specifications ..................302 2.1 Heat Pump ...................302 3.
Page 302
EDMT331529A 11.1 CDXS / FDXS..................344 11.2 FTXJ.....................345 11.3 FTXS ....................346 Residential Indoor Units with Connection to BP Units...
Page 303
EDMT331529A Power Supply 1. Power Supply Heat pump Indoor unit BP unit Power supply Slim ceiling mounted duct CDXS25EAVMA BPMKS967A3 1 phase, type BPMKS967A2 220-240/220-230V, CDXS35EAVMA 50/60Hz FDXS25CVMA FDXS35CVMA FDXS50CVMA FDXS60CVMA Wall mounted type FTXJ25NVMVW FTXJ25NVMVS FTXJ35NVMVW FTXJ35NVMVS FTXJ50NVMVW FTXJ50NVMVS FTXS20DVMA FTXS25EVMA FTXS35EVMA...
Page 304
Specifications EDMT331529A 2. Specifications Heat Pump Slim ceiling mounted duct type CDXS25EAVMA CDXS35EAVMA Model Cooling Heating Cooling Heating — — Front panel colour m³/min 8.7/8.0/7.3/6.2 8.7/8.0/7.3/6.2 Airflow rate (H/M/L/SL) 145/133/122/103 145/133/122/103 307/282/258/219 307/282/258/219 Type Sirocco fan Sirocco fan Motor output Speed Steps 5 Steps, Quiet, Auto...
Page 305
EDMT331529A Specifications Slim ceiling mounted duct type FDXS25CVMA FDXS35CVMA Model Cooling Heating Cooling Heating — — Front panel colour m³/min 9.5/8.8/8.0/6.7 10.0/9.3/8.5/7.0 Airflow rate (H/M/L/SL) 158/147/133/112 167/155/142/117 335/311/282/237 353/328/300/247 Type Sirocco fan Sirocco fan Motor output Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto Air filter Removable, Washable, Mildew proof...
Page 306
Specifications EDMT331529A Wall mounted type FTXJ25NVMVW FTXJ25NVMVS Model Cooling Heating Cooling Heating Front panel colour White Silver m³/min 8.3/6.3/4.0/2.1 10.4/7.5/5.8/3.3 8.3/6.3/4.0/2.1 10.4/7.5/5.8/3.3 Airflow rates (H/M/L/SL) 293/222/141/74 367/265/205/117 293/222/141/74 367/265/205/117 Type Cross flow fan Cross flow fan Motor output Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto Air direction control...
Page 307
EDMT331529A Specifications Wall mounted type FTXJ50NVMVW FTXJ50NVMVS Model Cooling Heating Cooling Heating Front panel colour White Silver m³/min 10.8/8.4/6.8/6.3 12.4/9.9/7.5/6.0 10.8/8.4/6.8/6.3 12.4/9.9/7.5/6.0 Airflow rates (H/M/L/SL) 381/297/240/222 438/350/265/212 381/297/240/222 438/350/265/212 Type Cross flow fan Cross flow fan Motor output Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto Air direction control...
Page 309
EDMT331529A Specifications Wall mounted type FTXS50FVMA FTXS60FVMA Model Cooling Heating Cooling Heating Front panel color White White m³/min 14.7 / 12.6 / 10.2 / 9.2 16.2 / 13.8 / 11.5 / 10.2 16.2 / 13.9 / 11.5 / 10.0 17.4 / 15.3 / 12.8 / 10.5 Airflow rate (H / M / L / SL) 245 / 210 / 170 / 153 270 / 230 / 192 / 170...
Page 310
Dimensions EDMT331529A 3. Dimensions Indoor Units 3.1.1 Slim Ceiling Mounted Duct Type CDXS25EAVMA / CDXS35EAVMA Residential Indoor Units with Connection to BP Units...
Page 311
EDMT331529A Dimensions FDXS25CVMA / FDXS35CVMA / FDXS50CVMA Residential Indoor Units with Connection to BP Units...
Page 312
Dimensions EDMT331529A FDXS60CVMA Residential Indoor Units with Connection to BP Units...
Page 313
EDMT331529A Dimensions 3.1.2 Wall Mounted Type FTXJ25NVMVW / FTXJ25NVMVS / FTXJ35NVMVW / FTXJ35NVMVS Residential Indoor Units with Connection to BP Units...
Page 314
Dimensions EDMT331529A FTXJ50NVMVW / FTXJ50NVMVS Residential Indoor Units with Connection to BP Units...
Page 315
EDMT331529A Dimensions FTXS20DVMA / FTXS25EVMA / FTXS35EVMA Residential Indoor Units with Connection to BP Units...
Page 316
Dimensions EDMT331529A FTXS50FVMA / FTXS60FVMA Residential Indoor Units with Connection to BP Units...
Page 317
EDMT331529A Dimensions FTXS71FVMA Residential Indoor Units with Connection to BP Units...
Page 318
Piping Diagrams EDMT331529A 4. Piping Diagrams Indoor Units 4.1.1 Slim Ceiling Mounted Duct Type CDXS25EAVMA / CDXS35EAVMA / FDXS25CVMA / FDXS35CVMA / FDXS50CVMA / FDXS60CVMA 4D045449U Residential Indoor Units with Connection to BP Units...
Page 319
EDMT331529A Piping Diagrams 4.1.2 Wall Mounted Type FTXJ25NVMVW / FTXJ25NVMVS / FTXJ35NVMVW / FTXJ35NVMVS 4D091640 FTXJ50NVMVW / FTXJ50NVMVS 4D091641 Residential Indoor Units with Connection to BP Units...
Page 320
Piping Diagrams EDMT331529A FTXS20DVMA / FTXS25EVMA / FTXS35EVMA 4D047912S FTXS50FVMA / FTXS60FVMA 4D040081Y Residential Indoor Units with Connection to BP Units...
Page 321
EDMT331529A Piping Diagrams FTXS71FVMA 4D040082W Residential Indoor Units with Connection to BP Units...
Page 322
Wiring Diagrams EDMT331529A 5. Wiring Diagrams Indoor Units 5.1.1 Slim Ceiling Mounted Duct Type CDXS25EAVMA / CDXS35EAVMA / FDXS25CVMA / FDXS35CVMA / FDXS50CVMA / FDXS60CVMA Residential Indoor Units with Connection to BP Units...
Page 323
EDMT331529A Wiring Diagrams 5.1.2 Wall Mounted Type FTXJ25NVMVW / FTXJ25NVMVS / FTXJ35NVMVW / FTXJ35NVMVS / FTXJ50NVMVW / FTXJ50NVMVS Residential Indoor Units with Connection to BP Units...
Page 324
Wiring Diagrams EDMT331529A FTXS20DVMA / FTXS25EVMA / FTXS35EVMA Residential Indoor Units with Connection to BP Units...
Page 325
EDMT331529A Wiring Diagrams FTXS50FVMA / FTXS60FVMA / FTXS71FVMA Residential Indoor Units with Connection to BP Units...
Page 326
Electric Characteristics EDMT331529A 6. Electric Characteristics Units Power supply Input (W) Model Volts Voltage range Cooling Heating CDXS25EAVMA 0.062 Max. 264V 50Hz 220-240V Min. 198V CDXS35EAVMA 0.062 FDXS25CVMA 0.062 FDXS35CVMA 0.062 Max. 264V 50Hz 220-240V Min. 198V FDXS50CVMA 0.130 FDXS60CVMA 0.130 FTXJ25NVMVW 0.029...
Page 329
EDMT331529A Fan Characteristics 8. Fan Characteristics Slim Ceiling Mounted Duct Type CDXS25EAVMA / CDXS35EAVMA C: 3D051853D FDXS25CVMA C: 3D045760G Residential Indoor Units with Connection to BP Units...
Page 330
Fan Characteristics EDMT331529A FDXS35CVMA C: 3D045761G FDXS50CVMA C: 3D045762H Residential Indoor Units with Connection to BP Units...
Page 331
EDMT331529A Fan Characteristics FDXS60CVMA C: 3D045763G Residential Indoor Units with Connection to BP Units...
Page 332
Sound Levels EDMT331529A 9. Sound Levels Indoor Units 9.1.1 Slim Ceiling Mounted Duct Type CDXS25EAVMA / CDXS35EAVMA Residential Indoor Units with Connection to BP Units...
Page 333
EDMT331529A Sound Levels FDXS25CVMA Residential Indoor Units with Connection to BP Units...
Page 334
Sound Levels EDMT331529A FDXS35CVMA Residential Indoor Units with Connection to BP Units...
Page 335
EDMT331529A Sound Levels FDXS50CVMA Residential Indoor Units with Connection to BP Units...
Page 336
Sound Levels EDMT331529A FDXS60CVMA Residential Indoor Units with Connection to BP Units...
Page 337
EDMT331529A Sound Levels 9.1.2 Wall Mounted Type FTXJ25NVMVW / FTXJ25NVMVS Residential Indoor Units with Connection to BP Units...
Page 338
Sound Levels EDMT331529A FTXJ35NVMVW / FTXJ35NVMVS Residential Indoor Units with Connection to BP Units...
Page 339
EDMT331529A Sound Levels FTXJ50NVMVW / FTXJ50NVMVS Residential Indoor Units with Connection to BP Units...
Page 340
Sound Levels EDMT331529A FTXS20DVMA / FTXS25EVMA Residential Indoor Units with Connection to BP Units...
Page 341
EDMT331529A Sound Levels FTXS35EVMA Residential Indoor Units with Connection to BP Units...
Page 342
Sound Levels EDMT331529A FTXS50FVMA Residential Indoor Units with Connection to BP Units...
Page 343
EDMT331529A Sound Levels FTXS60FVMA Residential Indoor Units with Connection to BP Units...
Page 344
Sound Levels EDMT331529A FTXS71FVMA Residential Indoor Units with Connection to BP Units...
Page 345
EDMT331529A Accessories 10. Accessories 10.1 Optional Accessories (for Indoor Unit) 10.1.1 Slim ceiling mounted duct type FDXS25CVMA CDXS25EAVMA Option name FDXS35CVMA FDXS60CVMA CDXS35EAVMA FDXS50CVMA Insulation kit for high humidity KDT25N32 KDT25N50 KDT25N63 C: 4D046409G 10.1.2 Wall mounted type FTXJ25NVMVW FTXJ25NVMVS FTXS20DVMA FTXS50FVMA FTXJ35NVMVW...
Page 346
Centre of Gravity EDMT331529A 11. Centre of Gravity 11.1 CDXS / FDXS CDXS25EAVMA / CDXS35EAVMA Unit (mm) 4D049301H FDXS25CVMA / FDXS35CVMA / FDXS50CVMA Unit (mm) 4D046081M Residential Indoor Units with Connection to BP Units...
Page 347
EDMT331529A Centre of Gravity FDXS60CVMA Unit (mm) 4D046082H 11.2 FTXJ FTXJ25NVMVW / FTXJ25NVMVS / FTXJ35NVMVW / FTXJ35NVMVS / FTXJ50NVMVW / FTXJ50NVMVS Unit (mm) 4D090742B Residential Indoor Units with Connection to BP Units...
Page 348
Centre of Gravity EDMT331529A 11.3 FTXS FTXS20DVMA / FTXS25EVMA / FTXS35EVMA Unit (mm) 4D048210Y FTXS50FVMA / FTXS60FVMA / FTXS71FVMA Unit (mm) 4D065095 Residential Indoor Units with Connection to BP Units...
Page 349
EDMT331529A Part 4 BP Units <BP Units> BPMKS967A3 BPMKS967A2 1. Specifications ..................348 1.1 BP Units ....................348 2. Dimensions ..................349 2.1 BP Units ....................349 3. Piping Diagrams..................351 3.1 BP Units ....................351 4. Wiring Diagrams..................352 4.1 BP Units ....................352 5. Electric Characteristics................353 6.
Specifications EDMT331529A 1. Specifications BP Units Model BPMKS967A3 BPMKS967A2 Power supply 1 phase, 220-240/220-230V, 50/60Hz Connectable indoor units 1~3 Units 1~2 Units Casing color Paintingless Power consumption Running current 0.05 0.05 Refrigerant type R410A Dimension (H×W×D) 180×294(650)*×350 Package dimension (H×W×D) 257×738×427 Machine weight Gross weight...
EDMT331529A Piping Diagrams 3. Piping Diagrams BP Units BPMKS967A3 INDOOR UNIT GAS SIDE ROOM A THERMISTOR ( DGA ) ( 15.9CuT ) LOCAL PIPING GAS SIDE REFRIGERANT FLOW ROOM B THERMISTOR ( DGB ) ( 15.9CuT ) HEATING LOCAL PIPING COOLING GAS SIDE ROOM C...
EDMT331529A Electric Characteristics 5. Electric Characteristics Units Power supply Input (W) Voltage Model Volts Cooling Heating range BPMKS967A3 Max. 264V 50Hz 220-240V 0.05 — — Min. 198V BPMKS967A2 BPMKS967A3 Max. 253V 60Hz 220-230V 0.05 — — Min. 198V BPMKS967A2 Symbols: MCA: Min. Circuit Amps (A) MFA: Max.
EDMT331529A Installation 8. Installation Accessories BPMKS967A3 For indoor unit side piping (gas) (For 3 rooms) Installation Manual (pipe joint) : 3pcs. 1pc. BPMKS967A2 (For 2 rooms) : 2pcs. For outdoor unit side piping (gas) Hanger metal (pipe joint) 1pc. 4pcs. For outdoor unit side piping (gas) Screws (pipe joint)
Page 358
Installation EDMT331529A Installation • This unit may be installed suspended from the ceiling or mounted on the wall. • This unit may only be installed, as shown in the diagram below. (The side should be facing upwards.) However, it may be freely installed in any direction forward or back, and to the sides. •...
Page 359
EDMT331529A Installation Installation For 3 rooms Wall-mounted (product dimensions and attachment bolt pitch) Indoor unit side piping Manufacturer’s label 4-Suspension bolt (M8-M10) Suspension bolt pitch Suspension bolt pitch Terminal (For A room) Wiring clamp 2×3-Brazing Wiring clamp Terminal (For B room) (304) Terminal (For C room) Electric box...
Page 360
Installation EDMT331529A Installation of the Unit Replacing the electric box • This unit has two different installation types: (1) ceiling-suspended type and (2) wall-mounted type. Printed circuit board • Choose the proper installation pattern according to the Reverse location of installation. position •...
Page 361
EDMT331529A Installation Installation of the Unit 6) Attach the printed circuit board and electrical equipment Printed circuit board cover to the other side and secure with the screws. Electrical Top surface of the unit equipment cover Insert the tabs fully. Ceiling-suspended type Screws 8 Hanger metal 7...
Page 362
Installation EDMT331529A Connection of Refrigerant Piping See the indoor and outdoor units installation manual for details on the size of connection piping to the indoor and outdoor units. About brazing pipes on site 1) Before brazing, remove the heat insulation. 2) Remove the blue-colored tape, and throw it out.
Page 363
EDMT331529A Installation Connection of Refrigerant Piping • After brazing and system leakage check, connect a Heat insulation Heat insulation heat insulation (field supply), and let it cure (field supply) (field supply) completely following the procedure illustrated right. Heat insulation 10 Use the heat insulation with the following Clasp Clasp...
Installation EDMT331529A C: 3P155399-1E BP Units...
Page 365
EDMT331529A Installation Connecting the Wiring 3) Follow the instructions on the wiring nameplate to connect the connection wires of indoor/outdoor units to terminal block numbers. (1, 2, 3, F and F ) Always fix each ground wire separately with a ground screw. (See the figure below.) NOTE: The terminal block numbers are arranged from top to bottom in order of 1, 2 and 3.
Installation EDMT331529A 4) Allow 300mm for the pulling-out section of harness. +300mm of slack +300mm of slack 5) Return the electrical equipment cover to its original position, and fix it with the screws. Screw (M4×12L) Install the electrical equipment cover. Operating Test Follow the “Operating test”...
Capacity Tables EDMT331529A 9. Capacity Tables Cooling Capacity for VRV Indoor Units Only (Te: 6ºC) When only VRV indoor units are connected RXYMQ4AVE Cooling capacity (Te: 6°C) Indoor air temp. (°CWB) Indoor air temp. (°CWB) Outdoor Outdoor Combina- Combina- 14.0 16.0 18.0 19.0...
Page 395
EDMT331529A Capacity Tables When only VRV indoor units are connected RXYMQ5AVE Cooling capacity (Te: 6°C) Indoor air temp. (°CWB) Indoor air temp. (°CWB) Outdoor Outdoor Combina- Combina- 14.0 16.0 18.0 19.0 20.0 22.0 24.0 14.0 16.0 18.0 19.0 20.0 22.0 24.0 tion (%) tion (%)
Page 396
Capacity Tables EDMT331529A When only VRV indoor units are connected RXYMQ6AVE Cooling capacity (Te: 6°C) Indoor air temp. (°CWB) Indoor air temp. (°CWB) Outdoor Outdoor Combina- Combina- 14.0 16.0 18.0 19.0 20.0 22.0 24.0 14.0 16.0 18.0 19.0 20.0 22.0 24.0 tion (%) tion (%)
Page 397
EDMT331529A Capacity Tables When only VRV indoor units are connected RXYMQ8AY1 Cooling capacity (Te: 6°C) Indoor air temp. (°CWB) Indoor air temp. (°CWB) Outdoor Outdoor Combina- Combina- 14.0 16.0 18.0 19.0 20.0 22.0 24.0 14.0 16.0 18.0 19.0 20.0 22.0 24.0 tion (%) tion (%)
Page 398
Capacity Tables EDMT331529A When only VRV indoor units are connected RXYMQ9AY1 Cooling capacity (Te: 6°C) Indoor air temp. (°CWB) Indoor air temp. (°CWB) Outdoor Outdoor Combina- Combina- 14.0 16.0 18.0 19.0 20.0 22.0 24.0 14.0 16.0 18.0 19.0 20.0 22.0 24.0 tion (%) tion (%)
EDMT331529A Capacity Tables Cooling Capacity for Mixed Combination or Only Residential Indoor Units When only Residential indoor units or VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ4AVE Cooling capacity (Capacity correction factor: 1.0) (Te: 9ºC) Indoor air temp.
Page 400
Capacity Tables EDMT331529A When VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ4AVE Cooling capacity (Capacity correction factor: 0.95) (Te: 9ºC) Indoor air temp. (°CWB) Indoor air temp.
Page 401
EDMT331529A Capacity Tables When VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ4AVE Cooling capacity (Capacity correction factor: 0.90) (Te: 9ºC) Indoor air temp. (°CWB) Indoor air temp.
Page 402
Capacity Tables EDMT331529A When VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ4AVE Cooling capacity (Capacity correction factor: 0.85) (Te: 9ºC) Indoor air temp. (°CWB) Indoor air temp.
Page 403
EDMT331529A Capacity Tables When only Residential indoor units or VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ5AVE Cooling capacity (Capacity correction factor: 1.0) (Te: 9ºC) Indoor air temp.
Page 404
Capacity Tables EDMT331529A When VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ5AVE Cooling capacity (Capacity correction factor: 0.95) (Te: 9ºC) Indoor air temp. (°CWB) Indoor air temp.
Page 405
EDMT331529A Capacity Tables When VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ5AVE Cooling capacity (Capacity correction factor: 0.90) (Te: 9ºC) Indoor air temp. (°CWB) Indoor air temp.
Page 406
Capacity Tables EDMT331529A When VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ5AVE Cooling capacity (Capacity correction factor: 0.85) (Te: 9ºC) Indoor air temp. (°CWB) Indoor air temp.
Page 407
EDMT331529A Capacity Tables When only Residential indoor units or VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ6AVE Cooling capacity (Capacity correction factor: 1.0) (Te: 9ºC) Indoor air temp.
Page 408
Capacity Tables EDMT331529A When VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ6AVE Cooling capacity (Capacity correction factor: 0.95) (Te: 9ºC) Indoor air temp. (°CWB) Indoor air temp.
Page 409
EDMT331529A Capacity Tables When VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ6AVE Cooling capacity (Capacity correction factor: 0.90) (Te: 9ºC) Indoor air temp. (°CWB) Indoor air temp.
Page 410
Capacity Tables EDMT331529A When VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ6AVE Cooling capacity (Capacity correction factor: 0.85) (Te: 9ºC) Indoor air temp. (°CWB) Indoor air temp.
Page 411
EDMT331529A Capacity Tables When only Residential indoor units or VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ8AY1 Cooling capacity (Capacity correction factor: 1.0) (Te: 9ºC) Indoor air temp.
Page 412
Capacity Tables EDMT331529A When VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ8AY1 Cooling capacity (Capacity correction factor: 0.95) (Te: 9ºC) Indoor air temp. (°CWB) Indoor air temp.
Page 413
EDMT331529A Capacity Tables When VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ8AY1 Cooling capacity (Capacity correction factor: 0.90) (Te: 9ºC) Indoor air temp. (°CWB) Indoor air temp.
Page 414
Capacity Tables EDMT331529A When VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ8AY1 Cooling capacity (Capacity correction factor: 0.85) (Te: 9ºC) Indoor air temp. (°CWB) Indoor air temp.
Page 415
EDMT331529A Capacity Tables When only Residential indoor units or VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ9AY1 Cooling capacity (Capacity correction factor: 1.0) (Te: 9ºC) Indoor air temp.
Page 416
Capacity Tables EDMT331529A When VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ9AY1 Cooling capacity (Capacity correction factor: 0.95) (Te: 9ºC) Indoor air temp. (°CWB) Indoor air temp.
Page 417
EDMT331529A Capacity Tables When VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ9AY1 Cooling capacity (Capacity correction factor: 0.90) (Te: 9ºC) Indoor air temp. (°CWB) Indoor air temp.
Page 418
Capacity Tables EDMT331529A When VRV and Residential indoor units are connected The capacity of outdoor unit can be calculated by interpolating between the two correction factor tables. RXYMQ9AY1 Cooling capacity (Capacity correction factor: 0.85) (Te: 9ºC) Indoor air temp. (°CWB) Indoor air temp.
Capacity Tables EDMT331529A Notes for Heating Capacity Characteristics (Heat Pump) The tables do not take account of the reduction in capacity when frost has accumulated or while the defrosting operation is in progress. The capacity values which take these factors into account, in other words the integrated heating capacity values, can be calculated as follows: Formula Integrated heating capacity = A...
EDMT331529A Part 6 Installation of Outdoor Units 1. Centre of Gravity .................436 2. Installation Manual ................438 2.1 RXYMQ4AVE ..................438 2.2 RXYMQ5AVE ..................454 2.3 RXYMQ6AVE ..................470 2.4 RXYMQ8AY1 / RXYMQ9AY1 ..............486 3. REFNET Pipe System.................502 3.1 Layout Example..................502 3.2 REFNET Joints and Headers ...............504 4.
Page 438
Centre of Gravity EDMT331529A 1. Centre of Gravity RXYMQ4AVE / RXYMQ5AVE Unit (mm) 4D091860B RXYMQ6AVE Unit (mm) 4D091861A Installation of Outdoor Units...
Page 439
EDMT331529A Centre of Gravity RXYMQ8AY1 / RXYMQ9AY1 Unit (mm) 4D086172C Installation of Outdoor Units...
Page 440
Installation Manual EDMT331529A 2. Installation Manual RXYMQ4AVE Please instruct the customer on how to operate the unit and keep it maintained The precautions described herein are classified as Warning and Caution, following which is the important safety information, it is strongly recommended to observe. This air conditioner comes under the term “appliances not accessible to the general public”.
Page 441
EDMT331529A Installation Manual Ask the dealer or specialized personnel to carry out the installation work. Do not install the machine by yourself. Otherwise, it may result in water leakage, electric shocks or fire hazards. Perform installation work following the instructions contained in this manual. Improper installation may result in water leakage, electric shocks or fire hazards.
Page 442
Installation Manual EDMT331529A 1P388325-1 Installation of Outdoor Units...
Page 443
EDMT331529A Installation Manual 1P388325-1 Installation of Outdoor Units...
Page 444
Installation Manual EDMT331529A 1P388325-1 Installation of Outdoor Units...
Page 445
EDMT331529A Installation Manual 1P388325-1 Installation of Outdoor Units...
Page 446
Installation Manual EDMT331529A 1P388325-1 Installation of Outdoor Units...
Page 447
EDMT331529A Installation Manual 1P388325-1 Installation of Outdoor Units...
Page 448
Installation Manual EDMT331529A 1P388318-1 Installation of Outdoor Units...
Page 452
Installation Manual EDMT331529A 1P388318-1 Installation of Outdoor Units...
Page 453
EDMT331529A Installation Manual 1P388318-1 Installation of Outdoor Units...
Page 454
Installation Manual EDMT331529A 1P388318-1 Installation of Outdoor Units...
Page 455
EDMT331529A Installation Manual 2P388309-1 Installation of Outdoor Units...
Page 456
Installation Manual EDMT331529A RXYMQ5AVE 1.This series air conditioner uses R410A (new) refrigerant. Strictly observe the precautions under the as there are strict requirements for how to prevent entry of impurities Refrigerant piping connection (mineral oils such as specialized lubricating oil and moisture) for R410A. Clean and dry Strict measures must be taken to keep impurities (including SUNISO oil and other mineral oils as well as moisture) out of the system.
Page 457
EDMT331529A Installation Manual Warning Ask the dealer or specialized personnel to carry out the installation work. Do not install the machine by yourself. Otherwise, it may result in water leakage, electric shocks or fire hazards. Perform installation work following the instructions contained in this manual. Improper installation may result in water leakage, electric shocks or fire hazards.
Page 458
Installation Manual EDMT331529A 1P388323-1 Installation of Outdoor Units...
Page 459
EDMT331529A Installation Manual 1P388323-1 Installation of Outdoor Units...
Page 460
Installation Manual EDMT331529A 1P388323-1 Installation of Outdoor Units...
Page 461
EDMT331529A Installation Manual 1P388323-1 Installation of Outdoor Units...
Page 462
Installation Manual EDMT331529A 1P388323-1 Installation of Outdoor Units...
Page 463
EDMT331529A Installation Manual 1P388323-1 Installation of Outdoor Units...
Page 464
Installation Manual EDMT331529A 1P388317-1 Installation of Outdoor Units...
Page 468
Installation Manual EDMT331529A 1P388317-1 Installation of Outdoor Units...
Page 469
EDMT331529A Installation Manual 1P388317-1 Installation of Outdoor Units...
Page 470
Installation Manual EDMT331529A 1P388317-1 Installation of Outdoor Units...
Page 471
EDMT331529A Installation Manual 2P388309-1 Installation of Outdoor Units...
Page 472
Installation Manual EDMT331529A RXYMQ6AVE 1.This series air conditioner uses R410A (new) refrigerant. Strictly observe the precautions under the as there are strict requirements for how to prevent entry of impurities Refrigerant piping connection (mineral oils such as specialized lubricating oil and moisture) for R410A. Clean and dry Strict measures must be taken to keep impurities (including SUNISO oil and other mineral oils as well as moisture) out of the system.
Page 473
EDMT331529A Installation Manual Warning Ask the dealer or specialized personnel to carry out the installation work. Do not install the machine by yourself. Otherwise, it may result in water leakage, electric shocks or fire hazards. Perform installation work following the instructions contained in this manual. Improper installation may result in water leakage, electric shocks or fire hazards.
Page 475
EDMT331529A Installation Manual <About carrying> Hold the 2 handles at both sides as shown in the figure below and move it slowly. (Pay attention not to touch the fins at the back.) Exhaust grille Inlet holes (Front) (Back) <Note> Conner Don’t place your fingers into the inlet holes of the casing while moving the unit.
Page 476
Installation Manual EDMT331529A 1P388321-1 Installation of Outdoor Units...
Page 477
EDMT331529A Installation Manual 1P388321-1 Installation of Outdoor Units...
Page 478
Installation Manual EDMT331529A 1P388321-1 Installation of Outdoor Units...
Page 479
EDMT331529A Installation Manual 1P388321-1 Installation of Outdoor Units...
Page 480
Installation Manual EDMT331529A 1P388312-1 Installation of Outdoor Units...
Page 484
Installation Manual EDMT331529A 1P388312-1 Installation of Outdoor Units...
Page 485
EDMT331529A Installation Manual 1P388312-1 Installation of Outdoor Units...
Page 486
Installation Manual EDMT331529A 1P388312-1 Installation of Outdoor Units...
Page 487
EDMT331529A Installation Manual 2P388306-1 Installation of Outdoor Units...
Page 488
Installation Manual EDMT331529A RXYMQ8AY1 / RXYMQ9AY1 Please instruct the customer on how to operate the unit and keep it maintained The precautions described herein are classified as Warning and Caution, following which is the important safety information, it is strongly recommended to observe. This air conditioner comes under the term “appliances not accessible to the general public”.
Page 489
EDMT331529A Installation Manual Warning Ask the dealer or specialized personnel to carry out the installation work. Do not install the machine by yourself. Otherwise, it may result in water leakage, electric shocks or fire hazards. Perform installation work following the instructions contained in this manual. Improper installation may result in water leakage, electric shocks or fire hazards.
Page 500
Installation Manual EDMT331529A 1P388311-1 Installation of Outdoor Units...
Page 501
EDMT331529A Installation Manual 1P388311-1 Installation of Outdoor Units...
Page 502
Installation Manual EDMT331529A 1P388311-1 Installation of Outdoor Units...
Page 503
EDMT331529A Installation Manual 2P388305-1 Installation of Outdoor Units...
Page 504
REFNET Pipe System EDMT331529A 3. REFNET Pipe System Layout Example 3.1.1 Heat Pump Use of the particular branch fitting appropriate to each individual unit type not only permits the pipes to be laid with ease but also increases the reliability of the system as a whole. Type Sample systems fitting...
Page 505
EDMT331529A REFNET Pipe System 3.1.2 Equivalent Piping Length of Joints and Header (Reference) φ6.4 φ9.5 φ12.7 φ15.9 φ19.1 φ22.2 Pipe Size* (mm) L Joints 0.16 0.18 0.20 0.25 0.35 0.40 REFNET Joint REFNET Header (m) * When the equivalent piping length in cooling operation is calculated, the gas pipe size is selected. When the equivalent piping length in heating operation is calculated, the liquid pipe size is selected.
Page 506
REFNET Pipe System EDMT331529A REFNET Joints and Headers 3.2.1 REFNET Joints For gas and liquid branch pipes Make sure that all branch pipes are fitted such that they branch either horizontally or vertically. When the size of the selected field piping is different from that of branch pipe then the connecting section should be cut with a pipe cutter as shown in the figure below.
Page 507
EDMT331529A REFNET Pipe System When the number of indoor units to be connected to the branch pipes is less than the number of branch pipes available for connection then cap pipes should be fitted to the surplus branches. When the size of the selected field piping is different from that of branch pipe then the connecting section should be cut with a pipe cutter as shown in the figure below.
Page 508
REFNET Joint and Header EDMT331529A 4. REFNET Joint and Header REFNET Joint (Branch Kit) KHRP26A22T Unit (mm) D3K05234A KHRP26A33T Unit (mm) D3K05235B Installation of Outdoor Units...
Page 509
EDMT331529A REFNET Joint and Header KHRP26A22T / KHRP26A33T 2P182411-1 Installation of Outdoor Units...
Page 510
REFNET Joint and Header EDMT331529A 2P182411-1 Installation of Outdoor Units...
Page 511
EDMT331529A REFNET Joint and Header REFNET Header (Branch Kit) KHRP26M22H Unit (mm) GAS SIDE JOINT INSULATION LIQUID SIDE JOINT INSULATION ACCESSORY REDUCER: GAS SIDE: 3 pcs LIQUID SIDE: 2 pcs PLUGGING TUBE: 1 SET INSULATION: 1 SET INSTALLATION MANUAL J: D3K03629C KHRP26M33H Unit (mm) GAS SIDE JOINT...
Page 512
REFNET Joint and Header EDMT331529A KHRP26M22H / KHRP26M33H 3P113151-1C Installation of Outdoor Units...
Page 513
EDMT331529A REFNET Joint and Header 3P113151-1C Installation of Outdoor Units...
EDMT331529A Part 7 Option of Control 1. Option List of Controllers..............526 1.1 Operation Control System Optional Accessories .........526 1.2 System Configuration ................527 1.3 Building Management System..............528 Option of Control...
Page 528
Option List of Controllers EDMT331529A 1. Option List of Controllers Operation Control System Optional Accessories For VRV indoor unit use Type Item FXDQ-PB FXFQ-S FXFQ-LU FXZQ-M FXUQ-A FXCQ-M FXKQ-MA FXDQ-NB Wireless H/P BRC7F634F BRC7E530W BRC7CB58 BRC7C62 BRC4C61 BRC4C65 Remote controller Wired BRC1C62 Navigation remote controller...
EDMT331529A Option List of Controllers For residential indoor unit use Type FTXS-D Item CDXS-EA FTXJ-N FTXS-E FDXS-C FTXS-F Remote controller Wireless — Note 1 Note 2 Wiring adaptor for time clock/remote controller KRP413AB1S (Normal open pulse contact/normal open contact) Remote controller loss prevention chain KKF917A4 KKF910A4 KKF917A4...
Page 530
Option List of Controllers EDMT331529A Building Management System Item Model No. Function Air-conditioning management system that can be controlled intelligent Touch intelligent Basic Hardware DCS601C51 Controller by a compact all-in-one unit. Touch Controller Additional 64 groups (10 outdoor units) are possible. Option Hardware DIII-NET plus adaptor DCS601A52...
Guide Specifications EDMT331529A 1. Guide Specifications Unit is air cooled, split type multi-system air conditioner consisting of plural indoor and outdoor units, having capability to cool or heat for the requirements of the rooms. Indoor Unit Various type's and capacity's indoor units can be connected to one refrigerant circuit and controlled individually. Refer to the chapter of Indoor Units for connectable models.
Page 536
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.