Remove any combustible material from within the area of the opening. No
combustible material can be allowed to come into contact with any area of the
appliance.
Fig. 7
Opening Sizes Width :-
375mm Minimum
440mm Maximum
Opening sizes Height :-
550mm Minimum
570mm Maximum
1.7

HEARTHS

This appliance must only be installed on to a concrete or non-combustible hearth.
The hearth material must be a minimum thickness of 12mm with the top surface at
least 50mm above the floor. The hearth must be fitted symmetrically about the fire
opening and have a minimum width of 760mm and a minimum projection of
300mm forwards from the fire opening.
1.8

SPILLAGE MONITORING SYSTEM

This appliance is fitted with an atmosphere sensing spillage monitoring system in
the form of an oxygen sensing burner. This is designed to shut the fire off in the
event of a partial or complete blockage of the flue causing a build up of
combustion products in the room in which the fire is operated. The following are
important warnings relating to this spillage monitoring system :-
1) The spillage monitoring system must not be adjusted by the installer.
2) The spillage monitoring system must not be put out of operation.
3) When the spillage monitoring system is exchanged only a complete original
manufacturers part may be fitted.
Ensure that the recess that is cut is to the required
dimensions and is screed level so that the firebox will
sit level within the recess.
9
Lintel must project
Minimum of 150mm
each side of the
opening