Flavel FVPC**MN Installation, Maintenance & User Instructions page 15

Kenilworth & linear powerflue fuel effect gas fures
Table of Contents

Advertisement

2.4.3
Mark the flue pipe in line with the outer wall surface so that it can be cut
to length.
NOTE :- When cutting the flue pipe to length, allowance for the rebate
on the fire surround used or false chimney breast constructed must be
taken into account.
2.4.4
Cut the flue to length, as marked in section 2.3.3. Secure the firebox
and run the gas supply into the firebox as detailed in section 2.5.
2.4.5
The electrical connection should be completed to the mains supply via a
3 amp fused switched spur or 3 pin socket and 3 amp plug. DO NOT
MAKE THE FINAL ELECTRICAL CONNECTION AT THIS POINT. The
product is supplied with 2.5 metres of three core mains cable, this cable
should be routed as inconspicuously as possible, i.e. chased into the
plaster.
2.4.6
Route the five core cable that runs from the firebox to the fan unit within
the opening, ensure that it is not trapped or coming into contact with the
firebox. Position the molex connector through the opening in the outer
wall, for connection to the fan chassis later in the installation.
2.4.7
Remove the fan box cover as shown below in Fig. 15 via the three
screws.
Fig. 15
2.4.8
Remove the 2 off lower self tapping screws and loosen the 2 off pan
head screws that hold the fan chassis in position and then lift the fan
chassis and gasket clear and store in a safe position.
15