13 – Introduction to thermographic inspections of electrical installations
< 5°C (9°F)
5–30°C (9–54°F)
>30°C (54°F)
The start of the overheat condi-
tion. This must be carefully
monitored.
Developed overheating. It must
be repaired as soon as possible
(but think about the load situa-
tion before a decision is made).
Acute overheating. Must be re-
paired immediately (but think
about the load situation before
a decision is made).