Conditions For The Boiler Room And The Environment; Combustion Air Supply Conditions; Conditions, Fuel - Buderus Logano G115/3 WS Installation And Service Instructions Manual

Low-temperature oil boiler
Hide thumbs Also See for Logano G115/3 WS:
Table of Contents

Advertisement

2
Product description
2.8.2

Conditions for the boiler room and the environment

Operating conditions
Temperature in the boiler room
relative humidity
Dust/airborne particles
Halogenated-hydrocarbon
compounds
Fans that extract air from the
boiler room.
Small animals
Fire safety
Flooding
Table 5 Boiler room and ambient conditions
2.8.3

Combustion air supply conditions

Operating conditions
Air intake flow cross-section for
combustion air drawn from
outside (divided between max. 2
apertures)
Table 6 Observe national regulations for boilers which draw their air supply from the boiler room.
If the burner is to be operated with sealed combustion by drawing its
combustion air solely from the outdoors, follow burner manufacturer's
specification.
2.8.4

Conditions, Fuel

Operating conditions
Permissible fuels for boilers
without integral burners
Contamination
Table 7 Fuels
10
+40 to +104 °F
max. 90 %
Excessive dust inside the boiler room must be avoided when the boiler is operating,
Combustion air supplied from outside must not be excessively loaded with dust or
•Air supply contaminated with dust from production and processing facilities, e. g.
The combustion air must be free from halogenated-hydrocarbon compounds.
•Identify the source of halogen-hydrocarbon compounds and seal it off. Where this is
impossible, route combustion air from areas that are not contaminated by halogen-
During burner operation, no mechanical air handling equipment may be operated that
Prevent small animals from entering the boiler room, particularly through the air inlet vents
Maintain clearances between the boiler and flammable materials in accordance with local
regulations. A minimum clearance of 16" is required. Never store flammable materials or
In case of an acute risk of flooding, disconnect the boiler in time from its fuel and power
supply before water enters the room. Any components or control equipment, which came
in contact with flood water, must be replaced before re-commissioning.
Boiler output (in case of
multi-boiler systems = total output)
< 170,000 Btu/hr
Notes – Requirement in greater detail
This boiler can be operated with #2 Fuel Oil ASTM D396-05 Type 2. Select a burner that is
suitable for this fuel typ.
Free of contaminants (for example dust, mist, humidity), i. e. a constant operation will not
lead to accumulation of deposits, in valves, strainers and filters and could lead to service
calls.
Notes – Requirement in greater detail
No condensation or precipitation inside the boiler room
•Dust from building work
airborne particles; if necessary, air filters should be fitted in case:
•Air supply contaminated with dust from dirt roads and paths.
quarries, mines, etc.
•Airborne particles from thistles and similar
hydrocarbon compounds.
could extract combustion air from the boiler room, e.g.:
•Exhaust hood
•Tumble dryer
•Ventilation equipment
– by fitting them with screens.
liquids in the vicinity of the boiler.
Ventilation air cross-section in square inches
Logano G115 WS US/CA – 6 720 813 418 (2019/09)
e. g.:
(unrestricted aperture)
At least 23.25 square inches