Quadra-Fire SAPH-MBK-IPI Installation Manual page 43

Hide thumbs Also See for SAPH-MBK-IPI:
Table of Contents

Advertisement

Install Horizontal Termination Cap
WARNING! Risk of Fire! The telescoping flue section of the
termination cap MUST be used when connecting vent.
• 1-1/2 (38 mm) minimum overlap of flue telescoping section
is required. Failure to maintain overlap may cause
overheating and fire.
• Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.
• Flash and seal as appropriate for siding material at outside
edges of cap.
• When installing a horizontal termination cap, follow the cap
location guidelines as prescribed by current ANSI Z223.1
and CAN/CGA-B149 installation codes and refer to
Section 6 of this manual.
CAUTION! Risk of Burns! Local codes may require
installation of a cap shield to prevent anything or anyone
from touching the hot cap.
NOTICE: For certain exposures which require superior
resistance to wind-driven rain penetration, a flashing kit and
HRC caps are available. When penetrating a brick wall, a
brick extension kit is available for framing the brick.
43
Quadra-Fire • SAPH-MBK-IPI, SAPH-D-PMH-IPI, SAPH-D-MBK-IPI, SAPH-D-CSB-IPI Installation Manual • 2343-980_R8 • 11/14
Note: when using termination caps with factory-supplied
heat shield attached, no additional wall shield firestop is
required on the exterior side of a combustible wall.
OUTER VENT
VENT DEPTH FROM BACK OF APPLIANCE TO
OUTSIDE SURFACE OF EXTERIOR WALL
Figure 7.18 Venting through the wall
HEAT SHIELD OR
EXTENDED
HEAT SHIELD
WALL SHIELD
FIRESTOP
SLIP SECTION
CAN BE EXTENDED
INNER VENT
SHEATHING
INTERIOR
(SEE CHART BELOW)
EXTERIOR

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents