1
Select the µA DC range on the multimeter. The multimeter
must have a resolution of at least 1µA [1].
Connect the multimeter to the ionization circuit in series [2].
Switch on the power supply to the heating system, see
section 79.
Put the boiler in service mode, see section 21.
During service mode, adjust the capacity to [l/2/5] = 25 %
with an 80-kW boiler or [l/2/0] = 20 % with a 100-kW boiler.
Check that the ionization current is at least 3 µA (microam-
peres) during service mode, operating code [-/a/\].
The actual value in practice is 5 - 40 µA.
Switch off the power supply to the heating system, see
section 72.
Remove the multimeter.
Connect the plug of the ionization electrode.
Close the boiler door as instructed in section 77.
Switch on the power supply to the heating system, see
section 79.
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
2
section 105 Checking the ionization electrode;
short circuit
Switch off the power supply to the heating system, see
section 72.
Open the boiler door as instructed in section 73.
3
1
Disconnect the plug and socket connection of the ionization
electrode [1].
Set the multimeter to "Measure resistance" [2].
Measure the ionization electrode to ground to make sure that
there is no short circuit between the ionization electrode and
ground. The electrical resistance between the ionization elec-
trode and ground must be infinite [3].
Attach the plug of the ionization electrode in reverse order.
Close the boiler door as instructed in section 77.
Switch on the power supply to the heating system, see
section 79.
Actions
7
2
77