Switch on the power supply of the heating system on the circuit
breaker.
Set the main switch on the BC10 to "1" (On).
8.1.15 Testing the ionization current
WARNING!
Avoid damage: do not push the measuring pin of
the volt-ohm-multimeter too deeply into the socket.
Switch off the power supply of the heating system on the circuit
breaker.
Set the main switch on the BC10 to "0" (Off).
Remove the casing.
Disconnect the plug and socket connection of the monitoring
cable.
Connect the measuring device in series (see fig. 25).
Set the multi-meter to DC µA.
Connect the heating system to the power supply, insert the
main fuse or switch on the circuit breaker.
Set the main switch on the BC10 to "1" (On).
Start up the boiler in accordance with the "Service Mode" menu.
See page 11 "Service Mode" menu.
Test the ionization current at partial load. The boiler is in part-
load operation as soon as, in the "Service Mode" menu, [l/3/0|
is selected. The ionization current must be > 1.4 DC µA.
Remove the measuring device.
Reconnect the plug and socket connection of the monitoring
cable if the ionization current is OK.
Fit the casing.
Switch on the power supply of the heating system on the circuit
breaker.
Set the main switch on the BC10 to "1" (On).
8.1.16 Checking the ionization electrode; cable
Switch off the power supply of the heating system on the circuit
breaker.
Set the main switch on the BC10 to "0" (Off).
Remove the casing.
Dismantle the plug and socket connection of the
ionization electrode.
Loosen the fastening screw of the UBA 3 (see fig. 26, pos. 1).
Remove the UBA 3 by pulling it forward as indicated by the
arrow (see fig. 26, pos. 2).
Logamax plus GB142-24/30/45/60 - We reserve the right to make any changes due to technical modifications!
fig. 25
Testing the ionization current
2
1
fig. 26
Dismantling the UBA 3
Actions
8
95