7
Actions
section 125 Replacing the automatic air purging system
Drain the boiler as indicated in section 75.
Open the boiler door as instructed in section 73.
3
Pull the clamp spring forwards [1] and remove the automatic
air purging system [2].
Note: The top of the automatic air purging system has two
cut-outs [3].
Install the new automatic air purging system so that the clamp
spring engages in both cut-outs.
Fill and purge the heating system and put the boiler into oper-
ation, see section 78.
88
3
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
section 126 Replacing/cleaning the burner
Disassemble the gas/air unit including the burner cover as
indicated in section 86.
Remove the burner gasket [1] and replace it if necessary.
Remove the burner [2].
Check the burner and the distributor plate for dirt and cracks
and clean or replace the burner.
Check the burner gasket for signs of ageing.
Replace the burner gasket if necessary.
Install the burner and the burner cover in reverse order.
Open the gas stop valve and put the boiler into chimney
sweep operation as instructed in section 81.
Check all couplings and locations in the gas train -which have
been disconnected to install the burner- for leaks. Use a
foaming agent which has been approved for gas leak testing.
If a gas leak is found: switch off the power supply to the heat-
ing system, see section 72, close the gas stop valve as indi-
cated in section 74 and deal with the cause of the gas leak.
Close the boiler door as instructed in section 77.
Switch on the power supply to the heating system, see
section 79.
Open the gas stop valve as indicated in section 81.