Disconnect the DHW temperature sensor plug [1].
Set the multimeter to "Measure resistance" [2].
Check the DHW temperature sensor cable for breaks.
The electrical resistance measured separately for every wire
Ω
must be approx. 0
[3].
Check the DHW temperature sensor cable for internal short
circuiting. The electrical resistance, measured between two
random wires, must be infinite.
Measure the electrical resistance over the DHW temperature
sensor cable to ground. The electrical resistance must be infi-
nite for every individual wire.
2
1
Set the multimeter to "Measure resistance" [1].
Check the cable of the DHW temperature sensor between
the connection tray and the UBA 3 mounting base for breaks.
The electrical resistance measured separately for every wire
Ω
must be approx. 0
[2]. Measure between the connection
tray and the black contacts (low-voltage connector pins 63
and 64) on the UBA 3 mounting base [3].
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
3
3
81-pin low-voltage connector
16-pin high-voltage connector
WA FW EV
Check the cable of the DHW temperature sensor between
the connection tray and the UBA 3 mounting base for internal
short circuiting. The electrical resistance, measured between
two random wires, must be infinite.
Measure the electrical resistance over the DHW temperature
sensor cable to ground. The electrical resistance must be infi-
nite for every individual wire.
Attach the relevant sensor plugs.
Install the UBA 3 in reverse order of removal.
Install the lid on the connection tray in reverse order.
Close the boiler door in reverse order.
Switch on the power supply to the heating system, see
section 79.
section 95
Replacing the feed, safety and return sensors
Drain the boiler, see section 75.
2
Switch off the power supply to the heating system, see
section 72.
Open the boiler door as instructed in section 73.
A
CAUTION!
Note that some water may escape when the sensor is
removed. Keep a bucket and a cleaning rag ready.
Disconnect the supply temperature sensor plug [1].
Remove the clamp spring of the supply temperature sensor
3
by moving it in the direction indicated by the arrow [2].
Remove the supply temperature sensor [3].
Actions
7