Buderus Logamax plus GB162-80 kW Service Instructions Manual page 52

Condensing gas boiler
Hide thumbs Also See for Logamax plus GB162-80 kW:
Table of Contents

Advertisement

6
Diagnosis
section 59
[7/c/\|
e
[2/3/1|
Step 1
 Press and hold the "
Step 2
Is an error code displayed again?
Step 3
 Check the meaning of the new fault, see section 29, and resolve the fault.
section 60
e
[7/h/\|
[3/2/8|
Step 1
 Check whether windmills, generators or other equipment are present which may have caused the main voltage
to be interrupted.
Step 2
Is this the case?
Step 3
Diagnosis: The fault is caused by the presence of windmills, generators or other equipment which may
cause the main voltage to be interrupted. Action: Place the affected equipment out of service.
Step 4
 Use a main voltage monitoring device to check, over a long period of time, whether the main voltage is actually
interrupted briefly.
Step 5
Has the main voltage actually been briefly interrupted?
Step 6
Diagnosis: The cause of the fault lies in the electrical system.
Action: Solve the problem in the electrical system.
section 61
e
[8/y/\|
[2/3/2|
Step 1
 Check that an external switch contact has been connected to the device, see section 116.
Step 2
Is an external switch contact connected?
Step 3
 Check that a connection is present, see section 116.
Step 4
Is there a connection?
Step 5
Diagnosis: There is no connection. Action: Restore the connection to the connection box, see section 116, [1].
Step 6
 Check the wire harness between the connection tray and the UBA 3 mounting base according to section 131.
Step 7
Is the wire harness okay?
Step 8
Diagnosis: The wire harness is defective. Action: Replace the wire harness or the affected part.
Step 9
 Check that the fault can be remedied by making a connection, see section 116.
Step 10
Has the fault been remedied?
Step 11
Diagnosis: The external switch contact has opened or a wire has broken in the external switch contact
wiring outside the boiler. Action: Remedy the cause of the external switch contact opening or replace the wiring.
52
Locking fault code: The power supply was interrupted during a locking fault
[4/a/\| [2/1/8|
[4/c/\| [2/2/4|
,
[4/u/\| [2/2/2| or [4/y/\| [2/2/3|.
c
" button for at least 2 seconds.
Blocking fault code: The main voltage has been briefly interrupted.
Operating code: The external switch contact has opened.
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
[4/e/\| [2/7/8|
[4/f/\| [2/1/9|
,
,
[4/l/\| [2/2/0|
,
,
Yes:
Step 3
No:
Section 67
Yes:
Step 3
No:
Step 4
Section 67
Yes:
Step 6
No:
Section 66
Section 67
Yes:
Step 9
No:
Step 3
Yes:
Step 6
No:
Step 5
Section 67
Yes:
Section 66
No:
Step 8
Section 67
Yes:
Step 11
No:
Step 6
Section 67