Checking the fan unit;
power supply cord (120 VAC)
H
DANGER OF FATAL ACCIDENT
A
due to electric shock!
DAMAGE TO THE INSTALLATION!
To prevent damage, do not insert the multimeter
measuring electrodes too far into the holes of the plug-
and-socket connection.
Switch off the power supply to the heating system, see
section 72.
Open the boiler door as instructed in section 73.
Remove the UBA 3 burner automat as instructed in
section 82.
Remove the cover from the connection tray, see section 114.
Undo the fan unit power supply cord plug as instructed in
section 86, [1].
Set the multimeter to "Measure resistance" [1].
Check the power supply cord of the fan unit for breaks. The
electrical resistance measured separately for every wire must
Ω
be approx. 0
[2]. Measure between the plug and the black
contacts (high-voltage connector pins 9, 10 and 11) on the
UBA 3 mounting base [3].
Check the power supply cord of the fan unit for internal short
circuiting. The electrical resistance, measured between two
random wires, must be infinite. See also section 131.
Remove the multimeter.
Connect the fan unit power supply plug in reverse order.
Install the UBA 3 burner automat in reverse order of removal.
Install the lid on the connection tray in reverse order.
Close the boiler door as instructed in section 77.
Switch on the power supply to the heating system, see
section 79.
62
81-pin low-voltage connector
16-pin high-voltage connector
3
2
1
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
section 85
Checking the fan unit;
tacho cable
H
DANGER OF FATAL ACCIDENT
A
due to electric shock!
DAMAGE TO THE INSTALLATION!
To prevent damage, do not insert the multimeter
measuring electrodes too far into the holes of the plug-
and-socket connection.
Switch off the power supply to the heating system, see
section 72.
Open the boiler door as instructed in section 73.
Remove the UBA 3 as instructed in section 82.
Remove the cover from the connection tray, see section 114.
Remove the tacho cable plug, see section 86, [2].
Set the multimeter to "Measure resistance" [1].
Connect the multimeter.
Check the fan unit tacho cable for breaks. The electrical
resistance measured separately for every wire must be
Ω
approx. 0
[2]. Measure between the plug and the black
contacts (low-voltage connector pins 16, 17, 44 and 45) on
the UBA 3 mounting base [3].
Check the fan unit tacho cable for internal short circuiting.
The electrical resistance, measured between two random
wires, must be infinite. See also section 131.
Remove the multimeter.
Connect the tacho cable plug in reverse order.
Install the UBA 3 in reverse order of removal.
Install the lid on the connection tray in reverse order.
Close the boiler door as instructed in section 77.
Switch on the power supply to the heating system, see
section 79.