6
Diagnosis
section 54
(continued)
Step 49
Check the following elements for contamination, damage and/or incorrect installation:
- Siphon, section 127;
- Air suction tube, section 1, [12];
- Seal and connection between venturi pipe and fan unit;
- Venturi pipe, see section 86;
- Orifice, see section 113;
- Fan unit;
- Seal and connection between fan unit and burner;
- Burner, section 126;
- Heat exchanger;
- Flue gas outlet and air inlet system;
- Ground wire insulation, see section 108.
Step 50
Are the above-mentioned components clean, free of damage and/or correctly installed?
Step 51
Diagnosis: The above components are dirty, damaged or not correctly installed.
Action: Clean, replace and/or re-install the relevant components.
Step 52
Check the ionization current as indicated in section 104.
Step 53
Is the ionization current okay?
Step 54
Check the plug-and-socket connection between the ionization electrode and wire harness as instructed in
section 104.
Step 55
Is the plug-and-socket connection okay?
Step 56
Diagnosis: The plug-and-socket connection has come loose.
Action: Connect the plug-and-socket connection correctly.
Step 57
Check the cable of the ionization electrode as indicated in section 106.
Step 58
Is the wiring okay?
Step 59
Diagnosis: The wire harness is defective. Action: Replace the wire harness or the affected part.
Step 60
Check the ionization electrode as indicated in section 105 and section 107.
Step 61
Is the ionization electrode okay?
Step 62
Diagnosis: The ionization electrode is defective. Action: Replace the ionization electrode, see section 103.
Step 63
Temporarily remove the combustion air supply and exhaust gas outlet connections from the top of the device.
Put the device into operation as instructed in section 20.
Note: Ensure that there is sufficient air supply during this test. Check that the fault has been rectified.
Step 64
Has the fault been remedied?
Step 65
Diagnosis: The cause of the fault is to be found in the air inlet/flue gas outlet system.
Action: Switch off the device and remedy the fault.
section 55
[6/c/\|
e
[2/2/8|
Step 1
Check the ionization electrode as indicated in section 105.
Step 2
Is the ionization electrode okay?
Step 3
Diagnosis: The ionization electrode is defective. Action: Replace the ionization electrode, see section 103.
48
Locking fault code: Flames (ionization current) were measured after a heat demand occurred,
but before opening the gas valve (section 1, [21]).
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
→
Yes:
Step 52
→
No:
Step 51
→
Section 67
→
Yes:
Section 67
→
No:
Step 54
→
Yes:
Step 57
→
No:
Step 56
→
Section 67
→
Yes:
Step 60
→
No:
Step 59
→
Section 67
→
Yes:
Step 63
→
No:
Step 62
→
Section 67
→
Yes:
Step 65
→
No:
Section 66
→
Section 67
→
Yes:
Section 66
→
No:
Step 3
→
Section 67