4
Operation
section 24
Step 22
Is there a current heat demand from the room or external temperature-dependent controller?
Step 23
Is the current heating-system supply temperature lower than 45 °F (7 °C)?
Step 24
The pump is run for 10 seconds in order to prevent it from seizing up.
Step 25
Have ten seconds elapsed?
Step 26
Is there a DHW heating system which has generated a demand?
Step 27
Is there a current heat demand from the room or external temperature-dependent controller?
Step 28
Is the current heating-system supply temperature lower than 45 °F (7 °C)?
Step 29
The LED "DHW demand" on the control panel (section 1, [4]) lights up.
[0/c/\|
Step 30
Operating code. The boiler prepares for a burner start-up whenever a heat demand arises. The fan unit
(section 1, [20]) and the pump are started. The glow ignitor (section 1, [27]) is activated.
[0/l/\|
Step 31
Operating code. The gas valve (section 1, [21]) is activated.
See also section 29 "Display codes and other symptoms", page 21.
Step 32
Maximum four ignition attempts are carried out. Does the ionization current exceed 1.4 microamperes within these
4 ignition attempts?
[-/h/\|
Step 33
Operating code: The device is in DHW mode.
See also section 29 "Display codes and other symptoms", page 21.
The LED "Burner operation" on the control panel (section 1, [4]) lights up. The startup load on the boiler is approx.
50 % for the purposes of flow monitoring and is then modulated up or down. The degree of modulation of the pump
will hardly vary during DHW mode; the pump will be running almost continuously at 100 %.
Step 34
Is there still a heat demand?
Step 35
Is the heating-system supply temperature 45 °F (25 °C) higher than the preset DHW temperature or higher than
200 °F (93 °C)?
[0/y/\|
Step 36
Operating code: The supply temperature sensor has measured a current heating supply temperature
higher than the supply temperature setting on the control panel (section 1, [4]), or higher than the
supply temperature calculated according to the heating curve or higher than the supply temperature
calculated according to the DHW mode.
Step 37
The LED "Burner operation" is extinguished.
Step 38
The fan unit (section 1, [20]) continues to run for max. 30 seconds.
Step 39
Has the heating system supply temperature fallen sufficiently?
Step 40
The gas valve (section 1, [21]) is closed and the burner is shut down.
Step 41
The LED "Burner operation" is extinguished.
Step 42
The LED "DHW demand" is extinguished.
[0/h/\|
Step 43
Operating code. The boiler is in standby mode. There is no current heat demand.
Start of pump over-run time via the tank for a period of approx. 60 seconds.
Start of air-side purging phase of the fan unit (section 1, [20]) for approx. 30 seconds.
See also section 29 "Display codes and other symptoms", page 21.
Step 44
Have approx. 30 seconds elapsed?
18
DHW operating phase
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
Yes:
Step 48
No:
Step 23
Yes:
Step 65
No:
Step 20
Yes:
Step 19
No:
Step 26
Yes:
Step 29
No:
Step 27
Yes:
Step 48
No:
Step 28
Yes:
Step 65
No:
Step 25
Yes:
Step 33
No:
Step 12
Yes:
Step 35
No:
Step 40
Yes:
Step 36
No:
Step 33
Yes:
Step 29
No:
Step 39
Yes:
Step 45
No:
Step 44