7
Actions
section 103 Replacing the ignition unit
H
DANGER OF FATAL ACCIDENT
due to electric shock!
Switch off the power supply to the heating system, see
section 72.
Open the boiler door as instructed in section 73.
Disconnect the plug of the glow ignitor as instructed in
section 101, [1] and or the plug of the ionization electrode as
instructed in section 104, [1].
Type A (old version)
Loosen both nuts [1].
Remove the retaining plate [2].
Remove the complete ignition unit: glow ignitor, ionization
electrode, sight glass with rubber seal, ignition unit housing
and bolts.
fig. 5 Old version ignition unit
Type B (new version)
Remove the complete ignition unit: ignition unit housing [1],
glow ignitor [2], ionization electrode [3], seal [4], rubber seal
with sight glass [5], bolts [6] and nuts [7].
7
1
fig. 6 New version ignition unit
A
DANGER OF FATAL ACCIDENT/FIRE
due to flue gas escaping or explosion of flamable gases.
All work on gas pipe work and fittings must be carried out
by authorized gas technicians.
76
2
1
3
4
5
2
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
A
DAMAGE TO THE INSTALLATION
due to incorrect glow ignitor assembly.
The glow ignitor is highly breakable. Handle with care.
Install the glow ignitor so that the lug of the heat
exchanger is located in the relevant opening in the glow
A
ignitor.
DAMAGE TO THE INSTALLATION
due to incorrect assembly.
Check that both bolts of the rubber seal with sight glass
are tightened evenly.
Install all new parts of tthe ignition unit (ignition unit housing
[1], glow ignitor [2], ionization electrode [3], seal [4], rubber
seal with sight glass [5], bolts [6] and nuts [7]).
Attach the plug of the glow ignitor and the ionization electrode
in reverse order.
Open the gas stop valve and put the boiler into chimney
sweep operation as instructed in section 81.
Check all couplings and locations in the gas train, which have
been disconnected, for leaks. Use a foaming agent which has
been approved for gas leak testing.
If a gas leak is found: switch off the power supply to the heat-
ing system, see section 72, close the gas stop valve as indi-
cated in section 74 and deal with the cause of the gas leak.
Close the boiler door as instructed in section 77.
Switch on the power supply to the heating system, see
section 79.
1
section 104 Measure the ionization current
Switch off the power supply to the heating system, see
section 72.
Open the boiler door as instructed in section 73.
6
Disconnect the plug of the ionization electrode [1].