6
Diagnosis
section 57
(continued)
Step 15
Diagnosis: There is an obstruction in the gas pipe. Action: Remove the obstruction.
Step 16
Has the gas supply pipe (and the gas tank, if relevant) been purged?
Step 17
Diagnosis: The gas supply pipe (and the gas tank, if relevant) has not been purged.
Action: Purge the gas supply pipe (and the gas tank, if relevant), see section 118.
Step 18
Check the plug-and-socket connection of the gas valve, see section 109.
Step 19
Is the plug-and-socket connection okay?
Step 20
Diagnosis: The plug-and-socket connection has come loose.
Action: Replace the plug-and-socket connection on the gas valve, see section 109.
Step 21
Check the gas valve power supply cord as indicated in section 111.
Step 22
Is the power supply cord okay?
Step 23
Diagnosis: The wire harness is defective. Action: Replace the wire harness or the affected part.
Step 24
Check that the overall gas supply network is of sufficient capacity.
Step 25
Is the overall gas supply network of sufficient capacity?
Step 26
Diagnosis: The gas supply network is not of sufficient capacity.
Action: Increase the capacity of the gas supply network.
Step 27
Diagnosis: The cause of the fault is to be found outside the boiler and the gas pipe work.
The gas supply pressure regulator may be defective. Action: Contact the gas utility company.
Step 28
Adjust the gas/air ratio, see section 119.
Step 29
Is the gas/air ratio okay?
Step 30
Diagnosis: The gas/air ratio setting is not okay. Action: Adjust the gas/air ratio, see section 119.
Step 31
Check that the correct orifice has been installed, see section 119 and 135.
Step 32
Has the correct orifice been installed?
Step 33
Diagnosis: The wrong orifice has been installed. Action: Install the correct orifice, see section 119 and 135.
Step 34
Check the following elements for contamination, damage and/or incorrect installation:
- Siphon, section 127;
- Air suction tube, section 1, [12];
- Seal and connection between venturi pipe and fan unit;
- Venturi pipe, see section 86;
- Orifice, see section 113;
- Fan unit;
- Seal and connection between fan unit and burner;
- Burner, section 126;
- Heat exchanger;
- Flue gas outlet and air inlet system;
- Ground wire insulation, see section 108.
Step 35
Are the above-mentioned components clean, free of damage and/or correctly installed?
Step 36
Diagnosis: The above components are dirty, damaged or not correctly installed.
Action: Clean, replace and/or re-install the relevant components.
Step 37
Check the ionization current as indicated in section 104.
50
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
→
Section 67
→
Yes:
Step 18
→
No:
Step 17
→
Section 67
→
Yes:
Step 21
→
No:
Step 20
→
Section 67
→
Yes:
Step 28
→
No:
Step 23
→
Section 67
→
Yes:
Step 27
→
No:
Step 26
→
Section 67
→
Section 67
→
Yes:
Step 31
→
No:
Step 30
→
Section 67
→
Yes:
Step 34
→
No:
Step 33
→
Section 67
→
Yes:
Step 37
→
No:
Step 36
→
Section 67