Buderus Logamax plus GB162-80 kW Service Instructions Manual page 46

Condensing gas boiler
Hide thumbs Also See for Logamax plus GB162-80 kW:
Table of Contents

Advertisement

6
Diagnosis
section 54
e
[6/a/\|
[2/2/7|
e
[6/a/\|
[2/2/7|
Step 1
Is the heating system propane gas-fired?
Step 2
 Contact the gas utility company to check that there is no nitrogen in the new or existing gas tank and the gas
supply pipe.
Step 3
Is there still nitrogen in the new or existing gas tank and the gas supply pipe?
Step 4
Diagnosis: There is nitrogen in the gas tank and the gas supply pipe.
Action: Remove the nitrogen in conjunction with the gas utility company.
Step 5
 Check that the device gas stop valve is open as instructed in section 81 and that the main gas stop valve is open.
Step 6
Are both gas stop valves open?
Step 7
Diagnosis: The device gas stop valve and/or the main gas stop valve is/are closed.
Action: Open the device gas stop valve as instructed in section 81 and open the main gas stop valve.
Step 8
 Check the static and dynamic gas supply pressures as indicated in section 117.
Step 9
Are the static and dynamic gas supply pressures correct?
Step 10
 Check that there is no obstruction in the gas pipe between the device gas stop valve and gas valve.
Step 11
Did you find an obstruction?
Step 12
Diagnosis: There is an obstruction in the gas pipe. Action: Remove the obstruction.
Step 13
 Check that there is no obstruction in other parts of the gas pipe.
Step 14
Did you find an obstruction?
Step 15
Diagnosis: There is an obstruction in the gas pipe. Action: Remove the obstruction.
Step 16
Has the gas supply pipe been purged?
Step 17
Diagnosis: The gas supply pipe has not been purged. Action: Bleed the gas supply pipe, see section 118.
Step 18
 Check that the glow ignitor activates when the operating code
Step 19
Does the glow ignitor activate when the operating code
Step 20
 Check the electrical resistance of the power supply cord of the glow ignitor as indicated in section 102.
Step 21
Is the power supply cord okay?
Step 22
Diagnosis: The wire harness is defective. Action: Replace the wire harness or the affected part.
Step 23
 Check the electrical resistance of the glow ignitor as indicated in section 102.
Step 24
Is the electrical resistance of the glow ignitor okay?
Step 25
Diagnosis: The glow ignitor is defective. Action: Replace the glow ignitor, see section 103.
46
Blocking fault code: Insufficient flame activity (ionization current) was measured during the
first, second or third burner ignition attempt (section 1, [23]).
Locking fault code: Insufficient flame activity (ionization current) was measured during the
fourth burner ignition attempt (section 1, [23]).
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
[0/c/\|
is displayed, see section 100.
[0/c/\|
is displayed?
Yes:
Step 2
No:
Step 5
Yes:
Step 4
No:
Step 5
Section 67
Yes:
Step 8
No:
Step 7
Section 67
Yes:
Step 16
No:
Step 10
Yes:
Step 12
No:
Step 13
Section 67
Yes:
Step 15
No:
Step 39
Section 67
Yes:
Step 18
No:
Step 17
Section 67
Yes:
Step 23
No:
Step 20
Yes:
Section 66
No:
Step 22
Section 67
Yes:
Step 26
No:
Step 25
Section 67