7
Actions
Install the lid on the connection tray in reverse order.
Install the UBA 3 in reverse order of removal.
Close the boiler door and install the casing of the pump group
in reverse order of removal.
Switch on the power supply to the heating system, see
section 79.
section 90
Checking the pump;
tacho cable
H
DANGER OF FATAL ACCIDENT
due to electric shock!
Switch off the power supply to the heating system, see
section 72.
Open the boiler door and remove the casing of the pump
group as instructed in section 73.
Remove the UBA 3 as instructed in section 82.
Remove the cover from the connection tray, see section 114.
A
B
Disconnect the pump tacho cable plug.
66
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
81-pin low-voltage connector
16-pin high-voltage connector
3
2
81-pin low-voltage connector
16-pin high-voltage connector
3
2
Set the multimeter to "Measure resistance" [1].
Connect the multimeter [2].
Check the tacho cable of the pump for breaks.
The electrical resistance measured separately for every wire
Ω
must be approx. 0
[2]. Measure between the plug and the
black contacts (low-voltage connector pins 67 and 68) on the
UBA 3 mounting base [3].
Check the tacho cable of the pump for internal short circuit-
ing. The electrical resistance, measured between two ran-
dom wires, must be infinite. See section 131.
Measure the electrical resistance over the pump tacho cable
to ground. The electrical resistance must be infinite for every
individual wire.
Attach the pump tacho cable plug in reverse order of removal.
Install the lid on the connection tray in reverse order.
Install the UBA 3 in reverse order of removal.
2
1
2
1