section 42
(continued)
Step 13
Diagnosis: The pressure sensor is defective. Action: Replace the pressure sensor, see section 128.
Step 14
Has the fault been remedied?
Step 15
 Check the pump activation as instructed in section 88.
Step 16
Is the activation okay?
Step 17
Diagnosis: The pump is defective. Action: Replace the pump, see section 92.
Step 18
 Check the pump power supply cord as instructed in section 89.
Step 19
Is the pump power supply cord okay?
Step 20
Diagnosis: The power supply cord is defective. Action: Replace the power supply cord of the pump.
section 43
e
[2/y/\|
[2/8/1|
Step 1
 Check that the pump has been purged correctly, see section 78.
Step 2
Has the pump been purged correctly?
Step 3
Diagnosis: There is air trapped in the pump. Action: Purge the pump, see section 78.
Step 4
 Check the pump for mechanical obstructions as instructed in section 87.
Step 5
Is the pump blocked?
Step 6
Diagnosis: The pump is blocked. Action: Attempt to start up the pump again as indicated in section 87 or replace
the pump as indicated in section 92.
Step 7
 Check that the tacho plug of the pump valve has been installed correctly, see section 90.
Step 8
Has the tacho plug of the pump been installed correctly?
Step 9
Diagnosis: The tacho plug of the pump has not been installed correctly.
Action: Install the tacho plug of the pump correctly, see section 90.
Step 10
 Check the electrical resistance of the tacho cable of the pump as indicated in section 89.
Step 11
Is the pump tacho cable okay?
Step 12
Diagnosis: The wire harness is defective. Action: Replace the wire harness or the affected part.
Step 13
 Check the pump power supply cord as instructed in section 89.
Step 14
Is the pump power supply cord okay?
Step 15
 Check the pump for contamination as instructed in section 87.
Step 16
Is the pump dirty?
Step 17
Diagnosis: The pump is dirty. Action: Clean the pump, see section 87.
Step 18
 Attempt to rectify the fault by temporarily replacing the pump, see section 92.
Step 19
Has the fault been remedied?
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
Operating code: The pump speed was found to be too high or too low while starting up
[0/u/\|. The modulating function of the pump is switched off. The pump continues to run, but
the pump speed is fixed.
Diagnosis
6
Yes:
Section 67
No:
Section 66
Yes:
Step 17
No:
Step 18
Section 67
Yes:
Section 66
No:
Step 20
Section 67
Yes:
Step 4
No:
Step 3
Section 67
Yes:
Step 6
No:
Step 7
Section 67
Yes:
Step 10
No:
Step 9
Section 67
Yes:
Step 13
No:
Step 12
Section 67
Yes:
Step 15
No:
Step 12
Yes:
Step 17
No:
Step 18
Section 67
Yes:
Section 67
No:
Section 66
41