section 42
(continued)
Step 13
Diagnosis: The pressure sensor is defective. Action: Replace the pressure sensor, see section 128.
Step 14
Has the fault been remedied?
Step 15
Check the pump activation as instructed in section 88.
Step 16
Is the activation okay?
Step 17
Diagnosis: The pump is defective. Action: Replace the pump, see section 92.
Step 18
Check the pump power supply cord as instructed in section 89.
Step 19
Is the pump power supply cord okay?
Step 20
Diagnosis: The power supply cord is defective. Action: Replace the power supply cord of the pump.
section 43
e
[2/y/\|
[2/8/1|
Step 1
Check that the pump has been purged correctly, see section 78.
Step 2
Has the pump been purged correctly?
Step 3
Diagnosis: There is air trapped in the pump. Action: Purge the pump, see section 78.
Step 4
Check the pump for mechanical obstructions as instructed in section 87.
Step 5
Is the pump blocked?
Step 6
Diagnosis: The pump is blocked. Action: Attempt to start up the pump again as indicated in section 87 or replace
the pump as indicated in section 92.
Step 7
Check that the tacho plug of the pump valve has been installed correctly, see section 90.
Step 8
Has the tacho plug of the pump been installed correctly?
Step 9
Diagnosis: The tacho plug of the pump has not been installed correctly.
Action: Install the tacho plug of the pump correctly, see section 90.
Step 10
Check the electrical resistance of the tacho cable of the pump as indicated in section 89.
Step 11
Is the pump tacho cable okay?
Step 12
Diagnosis: The wire harness is defective. Action: Replace the wire harness or the affected part.
Step 13
Check the pump power supply cord as instructed in section 89.
Step 14
Is the pump power supply cord okay?
Step 15
Check the pump for contamination as instructed in section 87.
Step 16
Is the pump dirty?
Step 17
Diagnosis: The pump is dirty. Action: Clean the pump, see section 87.
Step 18
Attempt to rectify the fault by temporarily replacing the pump, see section 92.
Step 19
Has the fault been remedied?
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
Operating code: The pump speed was found to be too high or too low while starting up
[0/u/\|. The modulating function of the pump is switched off. The pump continues to run, but
the pump speed is fixed.
Diagnosis
6
→
Yes:
Section 67
→
No:
Section 66
→
Yes:
Step 17
→
No:
Step 18
→
Section 67
→
Yes:
Section 66
→
No:
Step 20
→
Section 67
→
Yes:
Step 4
→
No:
Step 3
→
Section 67
→
Yes:
Step 6
→
No:
Step 7
→
Section 67
→
Yes:
Step 10
→
No:
Step 9
→
Section 67
→
Yes:
Step 13
→
No:
Step 12
→
Section 67
→
Yes:
Step 15
→
No:
Step 12
→
Yes:
Step 17
→
No:
Step 18
→
Section 67
→
Yes:
Section 67
→
No:
Section 66
41