6
Diagnosis
section 33
(continued)
Step 5
Does the LED "Central heat demand" light up?
Step 6
Check the ON/OFF controller according to section 114 or the RC regulator according to section 115.
Step 7
Does the boiler start heating operation within approx. 3 minutes
Step 8
Diagnosis: The thermostat cable is defective. Action: Replace thermostat cable.
Step 9
Diagnosis: The ON/OFF controller, the RC regulator or the RCC module, if present, is defective.
Action: Replace ON/OFF controller, RC regulator or RCC module. The RCC module is a suspended connection
tray, required for certain RC regulators.
Step 10
Has the fault been remedied?
Step 11
Check that the heating system supply temperature on the BC10 or on the RC regulator or ON/OFF controller has
been set high enough as instructed in section 81 or in the operating instructions of the regulator or controller.
Step 12
Is the heating-system supply temperature adjusted to a high enough setting?
Step 13
Are enough thermostatic valves open on the radiators, convectors, etc?
Step 14
Diagnosis: There are not enough thermostatic valves open on the radiators, convectors etc.
Action: Open more thermostatic valves.
Step 15
Diagnosis: The heating system supply temperature setting is too low. Action: Increase the heating system
supply temperature setting on the BC10 or on the RC regulator or ON/OFF controller as instructed in section 81 or
in the operating instructions of the regulator or controller.
Step 16
Check that the boiler performance has been set correctly in accordance with section 23 and 133.
Step 17
Is the boiler performance setting high enough?
Step 18
Diagnosis: The boiler performance setting is too low. Action: Adjust the boiler performance to a higher setting,
see section 23 and 133.
Step 19
Is the boiler performance of the wall-mounted condensing gas boiler sufficient to heat the building?
Step 20
Diagnosis: The boiler performance is too insufficient. Action: Install a larger heating boiler.
Step 21
Is there a hot-water supply?
Step 22
Check the movement of the servomotor of the three-way valve.
Step 23
Does the servomotor of the three-way valve move?
Step 24
Check that the three-way valve has been installed correctly.
Step 25
Has the three-way valve been installed correctly?
Step 26
Diagnosis: The three-way valve has not been installed correctly. Action: Install the three-way valve in the
correct way.
Step 27
Check the three-way valve activation.
Step 28
Does the activation of the three-way valve work correctly?
Step 29
Diagnosis: The servomotor of the three-way valve is defective. Action: Replace the servomotor of the three-
way valve.
34
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
[-/h/\|
?
→
Yes:
Step 11
→
No:
Step 6
→
Yes:
Step 8
→
No:
Step 9
→
Section 67
→
Yes:
Section 67
→
No:
Section 66
→
Yes:
Step 13
→
No:
Step 15
→
Yes:
Step 16
→
No:
Step 14
→
Section 67
→
Section 67
→
Yes:
Step 19
→
No:
Step 18
→
Section 67
→
Yes:
Step 21
→
No:
Step 20
→
Section 67
→
Yes:
Step 22
→
No:
Section 66
→
Yes:
Step 24
→
No:
Step 27
→
Yes:
Step 33
→
No:
Step 26
→
Section 67
→
Yes:
Step 29
→
No:
Step 30
→
Section 67