3 Functions of NB-Designer

3-5-11 Control Setting of Component

Option
Touch
Enable
Enabling
Input
Setting
Disable
Input
Conditional
Enabling
Show
Unable-to-
Input
Security
ON Delay
Setting
Confirm
Operation
Operation
Log
Min Inteval
Triggering
Macro
action
Write
Notice
* Please refer to 3-9-3 Macro Triggering (Page 3-268).
3-74

Control Setting of Component

Descriptions
Checking this option means the state value can be written into the controller by triggering the
effective area for the current component.
Checking this option means the state value cannot be written into the controller even when
triggering the effective touching area for the current component.
Security Level: Checking this option means only when the security level of the operator is
higher than the minimum security level already set, the current component can be touched,
and the state value can be written into the controller.
User Permission Control: Checking this option means the operator must have the permission to
touch the current component and write the state value into the controller.
Indirect reference: Checking this option means only when the state of the specified bit memory
or word memory meets the set conditions, the current component can be touched, and the
state value can be written into the controller.
Auto show login
Checking this option means the Password Input Screen Frame 9 (Login
screen
screen) will pop up automatically for the user to login when the security level
or the permission of the current user doesn't meet the requirement of the set
level or authority.
Checking this option allows Unable-to-Input figure will be displayed when the component is in
invalid to input. This function is optional only when [Enable Input] or [Conditional Enabling] is
checked; and touching invalid color can be set in [PT Property]-[PT Extended Properties].
When the current component is pressed consecutively for this set time, the state value can be
written only to the controller. The minimum unit is 100 ms. When this option is 0, this function is
invalid.
Checking this option means the Confirmation Screen will pop up automatically when the
current component is touched, and the state value can be written into the controller when
"YES" is clicked, while the operation will be cancelled automatically when the user have clicked
"Cancel" or haven't confirmed "YES" after the set "wait[s]" is exceeded.
Checking this option means the operation event will be recorded, and displayed through the
operation log element and the file in CSV format will be saved into the external memory.
Refers to the minimum interval between 2 operations for the same component or different
components. The minimum unit is second. When this option is 0, the minimum interval is
invalid.
Checking in this check box allows the macro which was specified before the current operation
was completed will be triggered and executed. *
Word
Notice Before
Written
Notice After
Written
Bit
Notice Before
Written
Notice After
Written
NB-series Programmable Terminals NB-Designer Operation Manual(V106)
Writes the write-value into the specified address before the
current operation is performed successfully.
Writes the write-value into the specified address after the
current operation is performed successfully.
Writes ON/OFF signal into the specified address before
the current operation is performed successfully.
Writes ON/OFF signal into the specified address after the
current operation is performed successfully.