5 Maintenance and Abnormality Handling
5-2

Checking and Cleaning

Please clean and check the NB Series periodically to ensure the NB Series always in the optimal
status.
Cleaning method
If the display part is dirty, then the screen will hard to see. Please perform cleaning periodically
according to the following points:
• During the daily cleaning, please use the dry soft cloth. But if use the dry soft cloth to clean
forcefully when it is too dirty, the front panel may be damaged. In this case, use the wet cloth to
clean it in advance.
• When the dirt cannot be cleaned by dry cleaning, please dip the cloth into the diluted neutral
washing agents (concentration of 2%) completely first, and then perform cleaning after the wet
cloth is wringed out.
• Waste, ethylene products or tape sticking to the Unit for a long period will generate dirt. If there is
dirt sticking to the Unit, please remove it during the cleaning.
Precautions for Safe Use
Do not use benzene, paint thinner, or other volatile solvents, and do not use chemically treated
cloths.
Checking method
Please perform checking once every 6 months to 1 year. But the frequent checking should be
necessary when the Unit is used in the extreme environments such as the environment with high
temperature, high humidity or more dust etc.
Checking items
Please check the following items for the criterion. If the item doesn't conform to the criterion, please
improve the surrounding environment, retighten the screw etc. to make it conform to the criterion.
Checking Items
Supply voltage
Surrounding environment
state
5-4
Checking Contents
Voltage fluctuation at
power terminal
Ambient temperature
(temperature inside
operation panel)
Ambient humidity
(humidity inside operation
panel)
Dirt
Oil mist sticking
NB-series Programmable Terminals NB-Designer Operation Manual(V106)
Criterion
Allowable voltage
fluctuation range
(DC24V, -15% to +15%)
°
°
0
50
C
~
10%
90% RH(without
~
condensation)
Without dirt
No oil penetrating into the
space between the front
panel and Unit box
Checking Method
Multimeter
Thermometer
Hygrometer
Visual check
Visual check