Removal Of Fan Motor - Daikin R-410A Service Manual

Sky-air indoor
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

Disassembly and Maintenance

1.11.8 Removal of Fan Motor

1
Warning
Procedure:
Step
Remove the terminal block
box cover according to the
procedure for removing the
switch box, then disconnect
the following connectors.
Transfer connector
Wired remote control
3
Swing motor
Humidity sensor
Connector built in the
switch box
Connector used for
power supply cables
5 5
1 Removing the bell mouth.
1
Disconnect the 2 remote
control cables and 3
power supply cables.
2
Disconnect the drain
pump and float switch
wiring from bell mouth.
*
(
1)
3
Remove the 5 mounting
screws on the bell mouth.
5–36
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure
For heat pump
For float switch
Power supply cable
Remote
controller
cable
*
1: At this time, do not cut the
clamp material attached to the
drain pan near the switch box.
Loosen the mounting screw to
remove the clamp material.
Part 5 – Disassembly and Maintenance
ESIEN05-04
Points

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents