Daikin R-410A Service Manual page 291

Sky-air indoor
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

ESIEN05-04
1.12.5 Removal of Swing Motor
Warning
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Removing the decoration
panel
Refer to the "Removal
of Decoration Panel"
2
Pull out the swing motor
harness from the wiring
groove.
3
Remove two mounting
screws for swing motor
mounting plate to remove
the plate.
4
Turn the horizontal vane
to downward manually,
and turn up the panel
side gear to disengage
the motor side gear.
5
Remove the swing
motor.
Part 5 – Disassembly and Maintenance
Procedure
Wiring groove
Disassembly and Maintenance
Fixing screw
(S2647)
(S2648)
1
Points
3
5
5
5–51