Possible system
The table below contains the possible system settings, which are displayed on the remote control if
settings
the TEST button is pushed twice shortly.
Size
Settings
Changing the mode
To enter the monitoring level and to change the maintenance mode settings, proceed as follows:
settings
Step
1
2
3
4
5
6
7
Part 4 – Commissioning and Test Run
Display
35
35
45
45
60
63
71
71
100
100
125
125
200
200
250
250
Action
Hold down the INSPECTION/TEST button for at least 4 s to enter the field setting mode.
Hold down the INSPECTION/TEST button for at least 4 s to enter the maintenance
mode.
Press the TEMPERATURE CONTROL buttons as many times as needed to select the
mode No. you want.
Press the TIMER SELECTION button as many times as needed to select the unit No. you
want.
Carry out the settings for modes 44 and 45. See "Maintenance Mode Settings" further in
this section.
Press the CONFIRMATION button to confirm the settings of modes 44 and 45.
Press the INSPECTION/TEST button to return to the normal operating mode.
Type
Software
Settings
FCQ
FHQ
FAQ
FFQ
5
FBQ
FUQ
FDQ, FDEQ
Field Settings
Display
FJ
HJ
AJ
GJ
JJ
3J
UJ
4
4–29
1
3
5