ESIEN05-04
3.6

Setting the Ceiling Height

Incorrectly setting
If you set the controller incorrectly, a connection mistake malfunction "UA" will appear on the remote
control display.
See 'Malfunctioning Field Setting Switch (UA)' on page 3–8.
Mode No. 13 or 23
Set the second code No., according to the tables below.
First code No. 0
FHQ
Second code No.
01
02
03
FAQ
Second code No.
01
02
03
FCQ and FUQ
Indoor unit
FCQ35-71
FCQ100-125-140
FUQ
Part 4 – Commissioning and Test Run
Ceiling-suspended type
Height < 2.7 m
2.7 m < height < 3.5 m
Not used
Wall-mounted type
Normal
High
Extra high
Second code No.
4-way outlet
01
< 2.7 m
02
< 3.0 m
03
< 3.5 m
01
< 3.2 m
02
< 3.6 m
03
< 4.2 m
01
< 2.7 m
02
< 3.0 m
03
< 3.5 m
Field Settings
3-way outlet
2-way outlet
< 3.0 m
< 3.5 m
< 3.3 m
< 3.8 m
< 3.5 m
< 3.6 m
< 4.2 m
< 4.0 m
< 4.2 m
< 4.2 m
< 3.0 m
< 3.5 m
< 3.5 m
< 3.8 m
< 3.8 m
1
3
4
5
4–23