ESIEN05-04
1.15.6 Removal of Fan Motor and Fan Rotor
Warning
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Removing the front grille in
accordance with "Removal
of Front Grille".
Removing the electrical box
in accordance with
"Removal of Electrical Box".
1 Removing the fan motor
1
Insert a Phillips tip
screwdriver into the air
outlet and remove the
screws fixing the fan
motor and fan rotor. (The
screws can be removed
without removing of
horizontal blade.)
2
Remove the two screws
on the bearing cover (1)
and (2) and dismantle the
covers.
3
Take out the fan motor
sideways.
2 Removing the fan rotor
Removing the heat
exchanger in accordance
with "Removal of Heat
Exchanger".
1
Remove the two screws
to dismantle the rotor
cover.
2
Pull the fan rotor out.
Part 5 – Disassembly and Maintenance
Procedure
Disassembly and Maintenance
Points
5–119
1
3
5
5

Hide quick links: