Malfunctioning Capacity Setting - Daikin R-410A Service Manual

Sky-air indoor
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

Error Codes
2.6
Malfunctioning Capacity Setting (AJ)
1
Error code
LED indications
3
3
Error generation
4
Causes
5
Capacity setting
adapter
3–38
AJ
The table below shows the LED indications.
Operation
Normal
Malfunctioning
The error is generated when the following conditions are fulfilled:
Condition
Description
1
The unit is in operation.
The PCB's memory IC does not contain the capacity code.
The capacity setting adapter is not connected.
2
The unit is in operation.
The capacity that is set, does not exist for that unit.
The possible causes are:
Malfunctioning capacity setting adapter connection
Malfunctioning indoor unit PCB.
The capacity is set in the PCB's memory IC. A capacity setting adapter that matches the capacity of
the unit is required in the following case:
In case the indoor PCB installed at the factory is for some reason changed at the installation site, the
capacity will not be contained in the replacement PCB. To set the correct capacity for the PCB you
have to connect a capacity setting adapter with the correct capacity setting to the PCB. The capacity
setting for the PCB will become the capacity setting of the adapter because the capacity setting
adapter has priority.
HAP (green)
c
c
ESIEN05-04
HBP (green)
c
c
Part 3 – Troubleshooting

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents