2) Types of PID control interfaces
Process quantity input data (frequency) and feedback input data can be combined as follows for the PID
control of the VF-S11:
Process quantity input data (frequency setting)
Setting method
(1) Internal potentiometer setting
(2) Panel input setting
(3) Internal preset-speed setting
(4) External analog setting
Note 1: About the setting of
Note 2: To make the inverter send out a signal that indicates whether the amount of feedback agree with (or
3) Setting PID control
Set " " in the extended parameter
6
(1)
(2)
4) Adjusting the PID control gain level
Adjust the PID control gain level according to the process quantities, the feedback signals and the object to
be controlled.
The following parameters are provided for gain adjustment:
VIB (DC: 0-10V)
because the VIA terminal is used for feedback signals.
reaches) the amount of processing, assign the function 52 or 53 to an unassigned output terminal.
You can also specify a frequency agreement detection range (
6.3.4.
Set parameters
(acceleration time), and
To limit the output frequency, set parameters
frequency). If process quantities are set from the operation panel, however, the process quantity setting
range will be limited by the settings of
Parameter
(P-gain)
0.01-100.0
(I-gain)
0.01-100.0
(D-gain)
0.00-2.55
Frequency setting mode selection 1
 /
/
-(
=0)
,
and
: Do not enable VIA using these parameters,
(PID control)
(deceleration time) to the system fitting values.
(upper limit frequency) and
and
.
Setting range
F-48
Feedback input data
External analog input
VIA (DC:4-20V / DC:0-10V)
). For more information, see
(lower limit
Default setting
0.30
0.20
0.00
E6581158