Toshiba TOSVERT VF-S11 Instruction Manual page 175

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

Communication function parameters (Common serial options)
The data transfer speed, parity type, inverter number, and communication error trip time can be set/edited by
operation panel operation or communication function.
Title
Function
Communication rate
Parity
Inverter number
Communication error trip time
Communication waiting time
Setting of master and slave
for communication between
inverters
Communication command point 1
setting
Communication command point 1
frequency
Communication command point 2
setting
Communication command point 2
frequency
Selection of communication
protocol
Block write data 1
Block write data 2
Adjustment range
0: 1200bps
1: 2400bps
2: 4800bps
3: 9600bps
4: 19200bps
0: NON (No parity)
1: EVEN (Even parity)
2: ODD (Odd parity)
0-255
0: Desabled (*)
1-100 (s)
0.00: Regular communication
0.01-2.00 (s)
0: Slave (0 Hz command issued in
case the master inverter fails)
1: Slave (Operation continued in
case the master inverter fails)
2: Slave (Emergency stop tripping
in case the master inverter fails)
3: Master (transmission of
frequency commands)
4: Master (transmission of output
frequency signals)
0-100 (%)
0-500.0 (Hz)
0-100 (%)
0-500.0 (Hz)
0: Toshiba inverter protocol
1: ModbusRTU protocol
0: No selection
1: Command 1
2: Command 2
3: Frequency command
4: Output data on the terminal
board
5: Analog output for
communications
F-81
E6581158
Default setting
3
1
0
0
0.00
0
6
0
0.0
100
50.0 (WP type)
60.0 (WN, AN type)
0
0
0