Control Circuit Terminals - Toshiba TOSVERT VF-S11 Instruction Manual

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

Power circuit
Terminal symbol
R/L1,S/L2,T/L3
U/T1,V/T2,W/T3
PA/+, PB
2
PC/-
PO, PA/+
The arrangement of power circuit terminals are different from each range.
Refer to 1.3.2.1).
2.3.2
The control circuit terminal board is common to all equipment.
Regarding to the function and specification of each terminal, please refer to the following table.
Refer to 1.3.2.3) about the arrangement of control circuit terminals.

Control circuit terminals

Terminal
Input/output
symbol
F
Input
R
Input
RES
Input
S1
Input
S2
Input
S3
Input
Input
PLC
(common)
Grounding terminal for connecting inverter. There are 3 terminals in total. 2 terminals in
the terminal board, 1 terminal in the cooling fin.
240V class: single-phase 200 to 240V-50/60Hz
three-phase 200 to 240V-50/60Hz
500V class: three-phase 380 to 500V-50/60Hz
600V class: three-phase 525 to 600V-50/60Hz
* Single-phase input: R/L1 and S/L2 terminals
Connect to a (three-phase induction) motor.
Connect to braking resistors.
Change parameters
This is a negative potential terminal in the internal DC main circuit. DC common power
can be input across the PA terminals (positive potential).
Terminals for connecting a DC reactor (DCL: optional external device). Shorted by a
short bar when shipped from the factory. Before installing DCL, remove the short bar.
Control circuit terminals
Function
Shorting across F-CC causes
forward rotation; open causes slow-
down and stop. (When ST is always
ON)
Shorting across R-CC causes
reverse rotation; open causes slow-
down and stop. (When ST is always
ON)
This inverter protective function is
disabled if RES are CC is connected.
Shorting RES and CC has no effect
when the inverter is in a normal
condition.
Shorting across S1-CC causes
preset speed operation.
Shorting across S2-CC causes
preset speed operation.
Shorting across S3-CC causes
preset speed operation.
External 24Vdc power input
When the source logic is used, a common
terminal is connected.
Terminal function
,
,
,
Electrical
specifications
No voltage
contact input
24Vdc-5mA or less
*Sink/Source/PLC
selectable using
SW1
24VDC
(Insulation
resistance: DC50V)
B-6
E6581158
if necessary.
Inverter internal circuits
+24V
SW1
PLC
SINK
SOURCE
PLC
820
4.7K
F∼S3
Factory default setting
WN, AN type : SINK side
WP type : SOURCE side