Adjustment Parameters; Pulse Train Output For Meters - Toshiba TOSVERT VF-S11 Instruction Manual

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

6.20 Adjustment parameters

6.20.1 Pulse train output for meters

: Logic output/pulse train output selection (OUT-NO)
: Pulse train output function selection (OUT-NO)
: Maximum nembers of pulse train
• Function
Pulse trains can be sent out through the OUT-NO output terminals.
To do so, it is necessary to select a pulse output mode and specify the number of pulses.
Ex.: When operations frequencies (0 to 60Hz) are put out by means of 0 to 600 pulses
=60.0,
Title
Logic output/pulse train
output selection (OUT-NO)
Pulse train output function
selection (OUT-NO)
Maximum numbers of
pulse train
Note 1: When item of f676 reachs "Reference of max. value", the number of pulse train set by f677 are
sent to output terminals (OUT-NO)
Note 2: The ON pulse width is maintained constant.
The ON pulse width is fixed at a width that causes the duty to reach 50% at the maximum pulse
number set with f677.
Therefore, the duty is variable.
For example, the ON pulse width is approximately 0.6 ms when f677=800, approximately 0.5
ms when f677=1000, or approximately 0.3 ms when f677=1600.
Note 3: The minimum pulse output rate is 38 pps. Keep in mind that no pulses can be put out at any rate
smaller than 38 pps.
=1,
=0,
=600
Function
0: Logic output
1: Pulse train output
0: Output frequency
1: Output current
2: Set frequency
3: DC voltage
4: Output voltage command value
5: Input power
6: Output power
7: Torque
8: Torque current
9: Motor cumulative load factor
10:Inverter cumulative load factor
11: PBR (braking reactor) cumulative
load factor
12:Frequency setting value (after PID)
13:VIA Input value
14:VIB Input value
15:Fixed output 1 (Output current: 100%)
16:Fixed output 2 (Output current: 50%)
17:Fixed output 3
(Other than the output current: 100%)
500-1600 (pps)
F-71
Adjustment range
E6581158
Reference
Default
of max.
setting
value
0
6
fh
185%
fh
150%
150%
185%
185%
250%
250%
100%
0
100%
100%
fh
10V/20mA
10V
185%
185%
100%
800