Toshiba TOSVERT VF-S11 Instruction Manual page 45

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

✩ The figure on the right shows an example of the
connection of input terminals VIA and VIB when they
are used as contact input terminals. This example
illustrates the connection when the inverter is used in
sink (Negative) logic mode.
Logic switching/Voltage-current output switching (slide switch)
(1)
Logic switching
Use SW1 to switch between logics.
Switch between logics before wiring to the inverter and without supplying power. If switching between
sink, source and PLC is done when power is turned on after switching or when the inverter is supplied
with power, the inverter might become damaged. Confirm it before supplying power.
(2)
Voltage-current output switching
Use the FM switch to switch between voltage output and current output.
Switch the FM terminal's voltage-current output before wiring to inverter or without supplying power.
Factory default settings of slide switches
SW1 : SINK (Negative) side (WN, AN type)
SOURCE (Positive) side (WP type)
FM : V side
VIA : V side
4.7kΩ
SW1
SOURCE
PLC
SINK
B-11
E6581158
P24
VIA
V
I
VIA(VIB)
CC
FM VIA
V
V
I
I