6.4

Basic parameters 2

6.4.1
• Function
6
Parameter setting
Switching motor characteristics via terminal input
: Base frequency 2
: Base frequency voltage 2
: Torque boost 2
: Motor electronic-thermal protection level 2
: Stall prevention level 2
Use the above parameters to switch the operation of two motors with a single inverter and to select
motor V/F characteristics (two types) according to the particular needs or operation mode.
Note: The
(V/F control mode selection) parameter is enabled only for motor1.
If motor 2 is selected, V/F control will be given constant torque characteristics.
Title
Function
Base frequency 2
Base frequency voltage 2
Torque boost 2
Motor electronic-thermal
protection level 2
Stall prevention level 2
Adjustment range
25.0-500.0 (Hz)
50-330 (V) : 240V class
50-660 (V) : 500 / 600V class
0.0-30.0 (%)
10-100 (%) / (A)
10-199 (%) / (A),
200 : Disabled
F-16
E6581158
Default setting
50.0 (WP type)
60.0 (WN, AN type)
230 (240V class)
460 (500V class)
575 (600V class)
Depending on model
(See Section 11, K-15)
100
150