WARNING
Grounding the rack installation: To avoid the potential for an electrical
shock hazard, you must include a third wire safety ground conductor
with the rack installation. If the server power cord is plugged into an
AC outlet that is part of the rack, then you must provide proper
grounding for the rack itself. If the server power cord is plugged into a
wall AC outlet, the safety-grounding conductor in the power cord
provides proper grounding only for the server. You must provide
additional, proper grounding for the rack and other devices installed
in it.
Overcurrent protection: The server is designed for an AC line voltage
source with up to 20 amperes of overcurrent protection. If the power
system for the equipment rack is installed on a branch circuit with more
than 20 amperes of protection, you must provide supplemental
protection for the server. If more than one server is installed in the
rack, the power source for each server must be from a separate branch
circuit. The overall current rating of a server configured with two
power supplies is less than 3 amperes.
CAUTION
Temperature: The operating temperature of the server, when installed in an
equipment rack, must not go below 5 °C (41 °F) or rise above 40 °C
(104 °F). Extreme fluctuations in temperature can cause a variety of
problems in your server.
Ventilation: The equipment rack must provide sufficient airflow to the front
of the server to maintain proper cooling. The rack must also include
ventilation sufficient to exhaust a maximum of 1023 BTU's per hour for the
server. The rack selected and the ventilation provided must be suitable to the
environment in which the server will be used.
WARNING
Do not attempt to modify or use an AC power cord that is not the exact
type required. You must use a power cord that meets the following
criteria:
1. Rating: For U.S./Canada cords must be UL Listed/CSA Certified type SJT,
18-3 AWG. For outside U.S./Canada cords must be flexible harmonized (<HAR>)
or VDE certified cord with 3 x 0.75 mm conductors rated 250 VAC.
2. Connector, wall outlet end: Cords must be terminated in grounding-type male plug
designed for use in your region. It must have certification marks showing
certification by an agency acceptable in your region and for U.S. must be rated
125% of overall current rating of the server.
3. Connector, server end: The connector that plugs into the AC receptacle on the
server must be an IEC 320, sheet C19, type female connector.
4. Cord length and flexibility: Cords must be less than 4.5 meters (14.76 feet) long.
62