3. Connector, server end: The connectors that plug into the
AC receptacle on the server must be an IEC 320, sheet C13, type
female connector.
4. Cord length and flexibility: Cords must be less than 4.5 meters
(14.76 feet) long.
CAUTION
Temperature: The temperature, at which the server operates when installed
in an equipment rack, must be maintained between 5 °C (41 °F) and 40 °C
(104 °F). Extreme fluctuations in temperature can cause a variety of
problems in your server.
Ventilation: The equipment rack must provide sufficient airflow to the front
of the server to maintain proper cooling. The rack must also include
ventilation sufficient to exhaust a maximum of 1023 BTU's per hour for each
installed server. The rack selected and the ventilation provided must be
suitable to the environment in which the server will be used.