Rigid Pipe Venting Systems - FPI P36D-NG Owners & Installation Manual

P36d zero clearance direct vent gas fireplace
Table of Contents

Advertisement

The minimum components required for a basic horizontal termination are:
1
Horizontal Termination Cap
1
90
o
Elbow
1
Rigid Pipe Adaptor
1
Wall Thimble
1
Length of pipe to suit wall thickness (see
chart)
Wall thickness is measured from the back
standoffs to the inside mounting surface of
termination cap. For siding other than vinyl
furring strips may be used, instead of the vinyl
siding standoff, to create a level surface to
mount the vent terminal. The Terminal must not
be recessed into siding. Measure the wall
thickness including furring strips.
If a Vinyl Siding Standoff is required (it must be
used with vinyl siding), measure to outside
surface of wall without siding and add 2
inches.
Vertical
Termination
Cap
Storm Collar
Flashing
Ceiling Firestop
Pipe Length
TM
The FPI AstroCap
and FPI Riser Vent terminal is certified for installations using FPI venting systems as well as Simpson Dura-Vent®, Direct Vent
GS, American Metal Products, and AmeriVent Direct Vent. FPI
International Ltd. Dura-Vent® and Direct Vent GS are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
FPI P36D Zero Clearance Direct Vent Gas Fireplace

RIGID PIPE VENTING SYSTEMS

Horizontal or Vertical Terminations
Wall Thickness
Wall Thickness
3-1/4"
7-3/4"
7-1/4"
4-1/4"
Vinyl Siding
Standoff (Optional)
Wall Thimble
Adj.Pipe Length
11" - 14-5/8"
o
90 Elbow
24" Pipe
Length
Rigid Pipe Adaptor
TM
, and FPI AstroCap
Flat Wall Installation
Vent Length
(inches)
Required (inches)
4"
-
5-1/2"
7"
-
8-1/2"
10"
- 11-1/2"
12"
9"
- 14-1/2"
11" - 14-5/8" Adj. Pipe
15"
- 23-1/2"
17" - 24" Adj. Pipe
Corner Installation
Vent Length
(inches)
Required (inches)
- 6-3/4"
11" - 14-5/8" Adj. Pipe
- 16-1/4"
17" - 24" Adj. Pipe
- 8-3/4"
6" + 12"
9" + 9"
- 5-3/4"
6" + 9"
Horizontal
Termination
Cap
WARNING:
Do not combine venting components from
different venting systems.
However use of the the AstroCap
Riser is acceptable with all systems.
This product has been evaluated by Intertek for
using a Dura-Vent Flue Adaptor in conjunction
with Selkirk Direct-Temp and Ameri Vent Direct
venting systems. Use of these systems with
the Direct Vent GS starting collar is deemed
acceptable and does not affect the Intertek WHI
listing of components.
TM
are the proprietary trademarks of FPI Fireplace Products
INSTALLATION
6"
9"
Alternate
Horizontal
Termination
Caps
TM
and FPI
23