Locating Your Gas Fireplace; Manufactured Home Additional Requirements; Heatwave Duct System (Optional); Heat Release Kit (Optional) - FPI P36D-NG Owners & Installation Manual

P36d zero clearance direct vent gas fireplace
Table of Contents

Advertisement

INSTALLATION
This includes:
1) Clocking the appliance to ensure the cor-
rect firing rate (rate noted on label 30,000
Btu/h) after burning appliance for 15 min-
utes.
2) If required, adjusting the primary air to
ensure that the flame does not carbon. First
allow the unit to burn for 15-20 min. to
stabilize.
CAUTION: Any alteration to the product
that causes sooting or carboning that
results in damage is not the responsibil-
ity of the manufacturer.
LOCATING YOUR
GAS FIREPLACE
1) When selecting a location for your fire-
place, ensure that the clearances outlined
on this page are met.
2) Provide adequate clearances for servic-
ing.
3) The appliance must be installed on a flat,
solid, continuous surface (e.g. wood, met-
al, concrete). This may be the floor, or
raised up on a platform to enhance its visual
impact. If the appliance is going to be in-
stalled on carpeting, combustible linoleum
tile or other combustible material other than
wood flooring, the appliance must be in-
stalled on a metal or wood panel extending
the full width and depth of the appliance.
4) The P36D Direct Vent Gas Fireplace can be
installed in a recessed position or framed
out into the room as in A, B, C, D. See
Diagram 1.
8
Diagram 1
A) Flat on Wall
B)
Flat on Wall Corner
C) Recessed into Wall/Alcove
D)
Corner
5) This appliance is Listed for bedroom instal-
lations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
6) The P36D Direct Vent Gas Fireplace is
approved for alcove installations, which
meet the clearances listed on this page.
7) We recommend that you plan your installa-
tion on paper using exact measurements
for clearances and floor protection before
actually installing this appliance. Have a
qualified inspector, dealer, or installer re-
view your plans before installation.
Note: For vent terminations see page 20.
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1) Ensure that structural members are not cut
or weakened during installation.
2) Ensure proper grounding using the #8
ground lug provided. See page 40.
DUCT SYSTEM
OPTION KIT #946-556
The HeatWave Air Duct Kit increases the
effectiveness of your fireplace by dispersing
warm air from the fireplace to remote locations
in the same room or other rooms in your home.
Up to two kits may be installed on the fireplace.
Please Note: Only 1 HeatWave kit may be
operated at one time. This includes the internal
blower option as well.
OPTIONAL
HEAT RELEASE
KIT #946-570
The Heat Release Kit expels warm air from the
fireplace to the outside of the building, allowing
the fireplace to be operated with less heat
entering the room. The kit may be used on either
the left or right side.
FPI P36D Zero Clearance Direct Vent Gas Fireplace