Pre-Occupancy Purge; Dehumidification And Reheat - Carrier WEATHERMAKER 48J Started Manual

Single package large rooftop units with comfortlink ti version 5.x controls sizes (020-060)
Table of Contents

Advertisement

IAO Econo Override
Pos (Configuration-+IAQ-+AQ.SP-+
-- This configuration
is the position that the econo-
mizer goes to when override is in effect.
Diff. Air Quality
Lo Limit (Configuration--+IAQ--+AQ.SP
-+DAQ.L)
-- This is the differential
CO2 level at which IAQ
control of the dampers will be initiated.
Diff. Air Quality
Hi Limit (Configuration-+IAQ-+AQ.SP
-+DAQ.H)
-- This is the differential
CO 2 level at which IAQ
control of the dampers
will be at maximum
and the dampers
will be at the Configuration-+IAQ-+DCV..C-+EC.MN.
DAQ
ppm
Fan
Off
Set
Point
(Con.figuration-+IAQ
-+AQ.SP-+D.EOF)
--
This is the CO 2 level at which the
indoor fan will be turned off.
DAQ
ppm
Fan
On
Set
Point
(Configuration
--+IAQ--+AQ.SP--+D.EON)
-- This is the CO2 level at which
the indoor fan will be turned on.
Diff. IAQ Responsiveness
(Con.figuration-+IAQ-+AQ.SP
-+IAQ.R)
-- This is the configuration
that is used to select the
IAQ response curves as shown in Fig. 13.
OAQ
Lockout
Value
(Con.figuration-+IAQ-+AQ.SP-+
OAQ.L)
-- This is the maxhnum
OAQ level above which de-
mand ventilation will be disabled.
User Determined
OAQ (Con.figuration-+IAQ--)AQ.SP-+
OAQ.U) -- If an OAQ sensor is unavailable, the user can
manually set the OAQ reading.
IAQ Low
Reference
(Con.figuration---_IAQ---_AQ.S.R---_
!Q.R.L)
-- This is the reference that will be used with a
non-Carrier IAQ sensor that may have a different characteristic
curve. It represents the CO2level at 4 mA.
IAQ
High
Reference
(Con.figuration --_IAQ---_AQ.S.R
-+IQ.R.H) -- This is the reference that will be used with a
non-Carrier IAQ sensor that may have a different characteristic
curve. It represents the CO2level at 20 mA.
OAQ
Low
Reference
((bnfiguration---_IAQ---_AQ.S.R
_OQ.R.L)
-- This is the reference that will be used with a
non-Carrier OAQ sensor that may have a different characteris-
tic curve. It represents the CO2 level at 4 mA.
OAQ High Reference
(Con.figuration---_IAQ---_AQ.S.R---_
OQ.R.H) -- This is the reference that will be used with a non-
Carrier OAQ sensor that may have a different characteristic
curve. It represents the CO2 level at 20 mA.
PRE-OCCUPANCY
PURGE-
The control has the option
for a pre-occupancy purge to refresh the air in the space prior to
occupancy.
This feature is enabled by setting (bnfiguration-+IAQ-+
IAQ.P-+IQ.PG to Yes.
The IAQ purge will operate under the following conditions:
• IQ.PG is enabled
• the unit is in the unoccupied state
• Current Time is valid
• Next Occupied Time is valid
• time is within two hours of the next occupied period
• time is within
the purge
duration (Configuration-+
IA Q--+IAQ.P--+IQ.R I)
If all of the above conditions are met, the following logic is
used:
If OAT > IQ.L.O
and OAT < OCSP
and economizer
is
available then purge will be enabled and the economizer
will
be colmnanded
to 100%.
If OAT < IQ.L.O
then the economizer
will be positioned
to
the
IAQ
Purge
LO
Temp
Min
Pos
((bnfiguration--+
IAQ--+IAQ.P--+IQ.RL )
If neither of the above are true then the dmnpers
will be
positioned
to the IAQ Purge HI Temp Min PUs ((bnfiguration
--+IAQ--+IAQ.P--+IQ.P.H)
If this mode is enabled the indoor fan and heat interlock
relay (VAV) will be energized.
IAQ Purge (Configuration
--+IA Q -+ IA Q.P --+IQ.PG)
--
This is used to enable IAQ pre-occupancy
purge.
IAQ
Purge
Duration
(Con.figuration--+IAQ--+IAQ.P--+
-- This is the maximum
amount of time that a purge
call
occur.
IAQ
Purge
Lo Temp
Min
Pos
(Configuration-+IAQ-+
IAQ.P-+IQ.RL)
--
This is used to configure
a low limit for
damper position to be used during the purge mode.
IAQ
Purge
Hi Temp
Min
Pos
(Configuration-+IAQ-+
IAQ.P-+IQ.RH)
-- This is used to configure a maximum
po-
sition for the dampers to be used during the purge cycle.
IAQ Purge
OAT Lockout
Temp
(Configuration-+IAQ-+
IAQ.P-+IQ.L.O)
--Nightthne
lockout
temperature
below
which the purge cycle will be disabled.
Dehumidification
and Reheat
E The Dehumidifi-
cation
function
will override
comfort
condition
set points
based on dry bulb temperature
and deliver cooler air to the
space in order to satisfy a humidity
set point at the space or
return air humidity
sensor. The Reheat function will energize a
suitable
heating
system
concurrent
with
dehumidification
sequence
should
the dehumidification
operation
result
in
excessive cooling of the space condition.
The dehumidification
sequence requires the installation
of a
space or return air humidity
sensor or a discrete switch input.
An ECB option is required
to accolmnodate
an RH (relative
humidity)
sensor connection.
A CEM (option or accessory)
is
required to accomodate
an RH switch. Reheat is possible when
multiple-step
staged gas control option or hydronic heat field-
installed coil is installed.
Reheat is also possible using a heat
reclahn
coil (field-supplied
and installed) or a DX (direct ex-
pansion) reheat coil.
Dehumidification
and reheat
control
are allowed
during
Cooling and Vent modes in the Occupied period.
On constant volume units using thermostat
inputs (C TYP =
3 or 4), the discrete switch input must be used as the dehumidi-
fication control input. The colrnnercial
Thermidistat
TM
device
is the recolmnended
accessory
device.
SETTING
UP THE SYSTEM
-- The settings for dehumidi-
fication can be found at the local display at Configuration-+
DEHU.
See Table 85.
Dehumidification
Configuration
(D.SEL)
-- The dehumidi-
fication configuration
can be set for the following settings:
• D.SEL
= 0 -- No dehumidification
and reheat.
• D.SEL
= 1 -- The control will perform
dehumidification
and reheat
with staged gas only.
• D.SEL
= 2 -- The control will perform
both dehumidifi-
cation and reheat with third party heat via an alarm relay.
In the case of D.SEL=2,
during
dehumidification,
the
alarm relay will close to convey
the need for reheat.
A
typical application
might be to energize
a 3-way valve to
perform DX reheat.
Dehumidification
Sensor (D.SEN)
-- The sensor can be con-
figured for the following settings:
• D.SEN
= 1 --
Initiated
by return
air relative
humidity
sensor.
• D.SEN
= 2 -- Initiated
by discrete input.
Economizer
Disable
in Dehum
Mode (D.E(:D)
--
This
configuration
determines
economizer
operation
during Dehu-
midification
mode.
• D.E(:D
= YES --
Economizer
disabled
during
dehu-
midification
(default).
• D.E(:D
= NO -- Economizer
not disabled
during dehu-
midification.
69