Carrier WEATHERMAKER 48J Started Manual page 65

Single package large rooftop units with comfortlink ti version 5.x controls sizes (020-060)
Table of Contents

Advertisement

CONSTANT VOLUME 2-STAGE CONTROL (BRCF = 1)
OPERATION
-- Two exhaust fan relays w illbeturned o nand
offbased o neconomizer
position. The twotripset p oints a re
BRP!
and BRP2.
If the economizer
is greater than or equal
to BRP1,
then power
exhaust
stage
1 is requested
and a
60-second
thner is initialized.
If the economizer
is 5% below
theBRP1,
then power exhaust stage 1 is turned off. Also, if the
economizer
position is less than BRP1 and the 60-second timer
has expired, power
exhaust
stage 1 is turned off. The same
logic applies to the second
power exhaust
stage, except the
BRP2
trip point is monitored.
If the economizer
position
is
greater than or equal to BRP2,
then power exhaust
stage 2
is energized
and a 60-second
timer is initialized.
If the econo-
mizer
is 5% below
the BRP2
the second
power
exhaust
stage turned off. If the economizer
is less than BRP2 and the
60-second
thner has expired,
second stage power
exhaust
is
turned off.
For BRCF=I,
the Table 82 illustrates
the power
exhaust
stages 1 and 2, relay combinations
based upon Configuration
-9BRMT
(4 or 6 motors).
MULTIPLE
POWER
EXHAUST
STAGE
BUILDING
PRESSURE
CONTROL
(BRCF
= 2) OPERATION
--
Building pressure control is active whenever
the supply fan is
running. The control algoritlnn to be used (BRSL=I)
is a timed
threshold
technique
for bringing
stages of power
exhaust on
and off.
The number of power exhaust stages available for this con-
trol algorithin is a function of the number of motors it supports.
This number of motors is defined by the Configuration-9BP
-9BRMT
configuration.
Table 83 illustrates
the staging tables
for this control algorithin based on BRMT.
The following
configurations
are used in the controlling
of
building pressure with this algorithin:
Configuration-9BP-9B.CFG-9BRHP
(building
pressure
high threshold level)
Configuration-9BP-9B.CFG-9BRLP
(building
pressure
low threshold level)
Configuration-9BP-9B.
CFG-9BR
TM (building
pressure
timer)
This control function is allowed to add or select power ex-
haust stages at any time, except that a delay time must expire
after a stage is added or subtracted.
Any time a stage change is
made, a timer is started which delays staging for 10 * BRTM
seconds.
The default
for BRTM
is 1, therefore
the delay
between stage changes is set to 10 seconds.
The logic to add or subtract a stage of power exhaust is as
follows:
If building
pressure
(Pressures-9AIR.P-9BP)
is greater
than the
building
pressure
set point
(Configuration-9
BP-gBPSP)
plus the building pressure high threshold
level
(Configuration-gBP-gB.CFG-gBRHP)
add
a stage
of
power exhaust.
Table 81 -- Building Pressure Configuration
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
BP
BUILDING PRESS. CONFIG
BP.CF
Building Press. Config
0-3
BLDG_CFG
O*
BP.RT
Bldg.Pres.PID Run Rate
5-120
sec
BPIDRATE
10
BP.P
Bldg. Press. Prop. Gain
0-5
BLDGP_PG
0.5
BP.I
Bldg.Press.lnteg.Gain
0-2
BLDGP_IG
0.5
BP.D
Bldg.Press.Deriv.Gain
0-5
BLDGP_DG
0.3
BP.SO
BP Setpoint Offset
0.0 - 0.5
"H20
BPSO
0.05
BP.MN
BP VFD Minimum Speed
0-100
%
BLDGPMIN
10
BP.MX
BP VFD Maximum Speed
0-1O0
%
BLDGPMAX
100
BP.FS
VFD/Act. Fire Speed/Pos.
0-1O0
%
BLDGPFSO
1O0
BP.MT
Power Exhaust Motors
1-2
PWRM
1*
BP.S
Building Pressure Sensor
Enable/Dsable
BPSENS
Dsable*
BP.R
Bldg Press (+/-) Range
0 - 1.00
"H20
BP_RANGE
0.25
BP.SP
Building Pressure Setp.
-0.25 -> 0.25
"H20
BPSP
0.05
BP.PI
Power Exhaust On Setp.1
0 - 100
%
PES1
35
BP.P2
Power Exhaust On Setp.2
0 - 100
%
PES2
75
B.CFG
BP ALGORITHM CONFIGS
BP.SL
Modulating PE AIg. Slct.
1-3
BPSELECT
1
BP.TM
BP PID Evaluation Time
0 - 10
min
BPPERIOD
1
BP.ZG
BP Threshold Adjustment
0.1 - 10.0
BPZ_GAIN
1
BP.HP
High BP Level
0 - 1.000
BPHPLVL
0.05
BP.LP
Low BP Level
0 - 1.000
BPLPLVL
0.04
•Some configurations are machine dependent.
Table
82 -- Power
Exhaust
Staging
(BP.CF=
1)
BP.MT= 1 (4 motors)
PE.A
PE.B
PE.C
Power Exhaust Stage 0
OFF
OFF
OFF
Power Exhaust Stage 1
OFF
ON
OFF
Power Exhaust Stage 2
ON
ON
ON
BP.MT= 2 (6 motors)
PE.A
PE.B
PE.C
Power Exhaust Stage 0
OFF
OFF
OFF
Power Exhaust Stage 1
OFF
OFF
ON
Power Exhaust Stage 2
ON
ON
ON
65