Carrier WEATHERMAKER 48J Started Manual page 64

Single package large rooftop units with comfortlink ti version 5.x controls sizes (020-060)
Table of Contents

Advertisement

ITEM
ECN. P
ECN. C
ACTV
DISA
UNAV
R.EC.D
DBC
DEW
DDBC
OAEC
DEC
EDT
OAT
FORC
SFON
CL OF
OAQL
HELD
DH.DS
O.AIR
OAT
OA.RH
OA.E
OA.D. T
Table 80 -- Economizer Run Status Table
EXPANSION
Economizer
Act.Curr.
Pos.
Economizer
Act.Cmd.
Pos.
Economizer
Active
?
ECON
DISABLING
CONDITIONS
Econ Act. Unavailable?
Remote
Econ. Disabled?
DBC - OAT Lockout?
DEW - OA Dewpt.Lockout?
DDBD-
OAT > RAT Lockout?
0 100 RANGE
0_100
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
OAEC- OA Enth Lockout?
DEC - Diff. Enth.Lockout?
EDT Sensor
Bad?
OAT Sensor
Bad ?
Economizer
Forced
?
Supply
Fan Not On 30s ?
Cool Mode Not In Effect?
OAQ Lockout in Effect ?
Econ Recovery
Hold Off?
Dehumid.
Disabled
Econ.?
OUTSIDE
AIR INFORMATION
Outside
Air Temperature
Outside
Air Rel. Humidity
Outside
Air Enthalpy
Outside
Air Dewpoint
Temp
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
YES/NO
I
I
NITS
CCN POINT
%
ECONOPOS
%
ECONOCMD
ECACTVE
ECONUNAV
ECONDISA
DBC
STAT
DEW- STAT
DDBCSTAT
OAECSTAT
DEC_STAT
EDT_STAT
OAT STAT
ECONFORC
SFONSTAT
COOL
OFF
OAQLOCKD
ECONHELD
DHDISABL
WRITE STATUS
forcible
dF
OAT
%
OARH
OAE
dF
OADEWTMP
forcible
forcible
Building Pressure Config (BRCF)
--
This
configuration
se-
lects the type of building pressure control.
• BR(T
= 0, No building pressure
control
• BR(T
= 1, constant
volume
two-stage
power
exhaust
based on economizer
position
• BR(T
= 2, lnultiple
stage
building
pressure
control
based on a building pressure
sensor
• BR(T
= 3, VFD building
pressure
control
based on a
building pressure
sensor
Building Pressure PID Run Rate (BRRT)
--
This configura-
tion selects the run thne of the PID algorithn.
This configura-
tion is only active when BRCF
= 3. It is recolrnnended
that this
value
not
be
changed
without
guidance
from
Service
Engineering.
Building Pressure Proportional
Gain (BRP) -- This configura-
tion selects the proportional
gain of the PID algorithin.
This
configuration
is only active when BRCF
= 3. It is recolrnnend-
ed that this value not be changed without guidance from Service
Engineering.
Building Pressure Integral Gain (BR1) --
This
configuration
selects the integral gain of the PID algorithin. This configuration
is only active when BRCF = 3. It is recolrnnended
that this val-
ue not be changed without guidance from Service Engineering.
Building Pressure Derivative
Gain (BRD) --
This configura-
tion selects the derivative gain of the PID algorithin.
This con-
figuration
is only active when BRCF
= 3. It is recolrnnended
that this value not be changed without
guidance from Service
Engineering.
Building Pressure Set Point Offset (BRSO)
-- This configura-
tion is the value below the building pressure set point to which
the building pressure must fall in order to turn offpower
exhaust
control. This configuration
is only active when BRCF = 3.
Building Pressure Minhnurn
Speed (BRMN)
-- This configu-
ration is the minilnurn
allowed VFD speed during building pres-
sure control. This configuration
is only active when BRCF = 3.
Building Pressure Maxhnurn
Speed (BRMX) -- This configu-
ration is the rnaxilnurn
allowed
VFD speed during building
pressure control. This configuration
is only active when BRCF
=3.
VFD Fire Speed (BRFS) -- This configuration is the VFD
speed ovemde when the control is in the purge or evacuation
slnoke control modes. This configuration is only active when
BRCF = 3.
Power Exhaust Motors
(BRMT)
-- This configuration
is ma-
chine dependent
and instructs
the building pressure
control
algorithin
as to whether the unit has 4 or 6 motors to control.
The motors are controlled
by three power exhaust relays A, B,
and C. These relay outputs are located at the local display un-
der Ou_outs---_FANS---_PE.A,B,
C
The following
table illustrates
the number
of motors each
relay is in control of based on BRMT:
BP.MT
PE A Relay
PE B Relay
PE
C Relay
1 (4motors)
1 Motor
2Motors
1 Motor
2 (6motors)
1 Motor
2Motors
3Motors
Building
Pressure
Sensor (BRS)
--
This
configuration
al-
lows the reading of a building pressure sensor when enabled.
This is automatically
enabled whenBRCF
= 2 or 3.
Building
Pressure
(+/-) Range (BRR)
-- This configuration
establishes the range in in. wg that a 4 to 20 mA sensor will be
scaled to. The control only allows sensors
that measure
both
positive and negative pressure.
Building
Pressure
SETP (BRSP)
--
This set point
is the
building pressure control set point. If the unit is configured
for
modulating
building pressure
control, then this is the set point
that the control will control to.
Power Exhaust on Setp. 1 (BRP1)
--
When
configured
for
building pressure control type BRCF = 1 (constant volume two-
stage control), the control will turn on the first power exhaust
fan when the econornizer's
position exceeds this set point.
Power Exhaust on Setp.1 (BRP2)
--
When
configured
for
building pressure control type BRCF = 1 (constant volume two-
stage control), the control will turn on the second power exhaust
fan when the economizer's
position exceeds this set point.
Modulating
PE Algorithin
Select (BRSL) -- This configuration
selects the algorithin used to step the power exhaust stages. This
lnust be set to 1 at all thnes. The other selections are not used.
Building
Pressure
PID Evaluation
Time (BP. TM)
--
This
configuration
is the run time rate of the multiple stage (lnodu-
lating) power exhaust algorithin (BR(T=2).
Building
Pressure
Threshold
Adjustment
(BRZG)
--
This
configuration
is not used. It currently has no effect on building
pressure control.
High Building
Pressure
Level (BRHP)
--
This
configura-
tion is the threshold level above the building pressure set point
used to control stages of power exhaust when BRSL=I.
Low Building
Pressure
Level (BRLP)
--
This configuration
is the threshold level below the building pressure set point used
to control stages of power exhaust when BRSL=I.
64