Carrier WEATHERMAKER 48J Started Manual page 122

Single package large rooftop units with comfortlink ti version 5.x controls sizes (020-060)
Table of Contents

Advertisement

Table 119 -- Controls Expansion Board (CEM) Inputs
POINT
I/O POINT
PLUG AND PIN
POINT DESCRIPTION
SIGNAL
PIN(S)
PORT STATE
NAME
NAME
REFERENCE
INPUTS
SFS
Supply Fan Status switch
DI 1
37, 1-2
2
0 = 24vac, 1= 0vac
DMD
SWl
Demand
Limit - SWl
DI 2
J7, 3-4
4
0 = 24vac, 1= 0vac
DMD
SW2/
Demand
Limit - SW2/
DHD]SClN
Dehumidification
Switch Input
DI 3
J7, 5-6
6
0 = 24vac, 1= 0vac
PRES
Pressurization
DI 4
J7, 7-8
8
0 = 24vac, 1= 0vac
EVAC
Evacuation
DI 5
J7, 9-10
10
0 = 24vac, 1= 0vac
PURG
Purge
DI 6
J7, 11-12
12
0 = 24vac, 1= 0vac
IAQIN
Indoor Air Quality Switch
DI 7
J7, 13-14
14
0 = 24vac, 1= 0vac
AN7
J6, 1-3
2 (1 = loop power)
(O-20mA input)
DMDLMTMA
4-20mA Demand Limit
AN8
J6, 4-6
5 (4 = loop power)
(O-20mA input)
EDTRESMA
4-20mA Evaporator
Discharge SP Reset
AN9
J6, 7-9
8 (7 = loop power)
(O-20mA input)
OAQ
Outside Air CO2 Sensor
AN10
J6, 10-12
11 (10 = loop power)
(O-20mA input)
SPRESET
SP Reset milliamps
AN10
J6, 10-12
11 (10 = loop power)
(O-20mA input)
CEM 10K1/
CEMAN1
lOktemp
J5,1-2/
CEM 4201
CEM AN1 4-20 ma J5,1-2
AN1
J5, 1-2
1
(thermistor,
ohms)
CEM 10K2/
CEM AN2 1Ok temp J5,3-4/
CEM 4202
CEM AN2 4-20 ma J5,3-4
AN2
J5, 3-4
3
(thermistor,
ohms)
CEM 10K3/
CEM AN3 1Ok temp J5,5-6/
AN3
J5, 5-6
5
(thermistor,
ohms)
CEM 4203
CEM AN3 4-20 ma J5,5-6
CEM 10K4/
CEM AN4 1Ok temp J5,7-8/
AN4
J5, 7-8
7
(thermistor,
ohms)
CEM 4204
CEM AN4 4-20 ma J5,7-8
AN5
J5, 9-10
9
(thermistor,
ohms)
AN6
J5, 11-12
11
(thermistor,
ohms)
SCROLLING
MARQUEE-
This device is the keypad in-
terface used to access
the control information,
read sensor
values, and test the unit. The scrolling
marquee
display is a
4-key, 4-character,
16-segment
LED
display
as well as an
Alarm Stares LED. See Fig. 30. The display is easy to operate
using 4 buttons
and a group of 11 LEDs that indicate
the
following menu structures:
Run Status
Service Test
Temperatures
Pressures
Set points
Inputs
Outputs
Configuration
Timeclock
Operating Modes
Alarms
Through
the scrolling marquee
the user can access all the
inputs and outputs to check on their values and status. Because
the unit is equipped
with suction
pressure
transducers
and
discharge
saturation
temperature
sensors
it can also display
pressures typically obtained from gages. The control includes a
full alarm history, which can be accessed
from the display. In
addition,
through the scrolling marquee
the user can access a
built-in test routine that can be used at start-up colmnission
and
to diagnose
operational
problems
with the unit. The scrolling
marquee
is located in the main control box and is standard on
all units.
O
Run Status
O
Configuration
qime
Clock
@AEarm
Status
@Operath_gModes
@/Uarms
]
Fig. 30-
Scrolling Marquee
SUPPLY FAN -- The size 020 to 050 units are equipped with
two 15 x ll-in,
forward-curved
fans. The size 051 and 060
units have three 15 x 11-in. fans. They are on a colranon
shaft
and are driven by single belt drive 3-phase motor. The fan is
controlled
directly by the (_n_folTLink
TM
controls.
VARIABLE
FREQUENCY
DRIVE
(VFD) --
On variable
volume units, the supply fan speed is controlled
by a 3-phase
VFD. The VFD is located in the fan section behind a remov-
able panel as shown in Fig. 24 and 25. The VFD speed is
controlled
directly by the (_,fortLink
controls through a 4 to
20 mA signal based on a supply
duct pressure
sensor. The
inverter has a display, which can be used for service diagnos-
tics, but setup of the supply duct pressure set point and control
loop factors is done through the scrolling marquee
display. The
VFD is powered
during normal operation to prevent condensa-
tion from forming on the boards during the off mode and is
stopped by driving the speed to 0 (by sending a 2 mA signal to
the VFD).
The A Series units use ABB ACH550
VFDs. The interface
wiring for the VFDs is shown in Fig. 31. Terminal designations
are shown in Table 121.
Table 120 -- IGC Board Inputs and Outputs
] CONNECTOR
POINT NAME
POINT
DESCRIPTION
PIN NO.
INPUTS
RT
24 Volt Power Supply
R1 ,C
W
Heat Demand
2
G
Fan
3
LS
Limit Switch
7,8
RS
Rollout
Switch
5,6
SS
Hall Effect Sensor
1,2,3
CS
Centrifugal
Switch
(Not Used)
9,10
FS
Flame
Sense
FS
OUTPUTS
CM
Induced
Draft Motor
CM
IFO
Indoor
Fan
IFO
R
24 Volt Power Output
(Not Used)
R
SPARK
Sparker
LED
D sp ay LED
122