Carrier WEATHERMAKER 48J Started Manual page 95

Single package large rooftop units with comfortlink ti version 5.x controls sizes (020-060)
Table of Contents

Advertisement

Table 114 -- Alert and Alarm Codes (cont)
ALARM
OR
RESET
DESCRIPTION
ACTION TAKEN BY CONTROL
PROBABLE
CAUSE
ALERT
METHOD
NUMBER
T300
Space Temperature
Below Limit
Stop cooling,
but continue
to heat
Automatic
Outdoor dampers stuck, no load
T301
Space Temperature
Above Limit
Stop heating, but continue
to cool
Automatic
High load, dampers open
Dampers open, check configuration
T302
Supply Temperature
Below Limit
Continue to run unit
Automatic
setpoint
Dampers open, check configuration
T303
Supply Temperature
Above Limit
Continue to run unit
Automatic
setpoint
Dampers open, check configuration
T304
Return Temperature
Below Limit
Continue to run unit
Automatic
setpoint
Dampers open, check configuration
T305
Return Temperature
Above Limit
Continue to run unit
Automatic
setpoint
T308
Return Air Relative Humidity Below Limit
Alert
Automatic
Configuration
error, or sensor error
Dampers open, check configuration
T309
Return Air Relative Humidity Above Limit
Continue to run unit
Automatic
setpoint
T310
Supply Duct Static Pressure Below Limit
Continue to run unit
Automatic
VFD problem, broken fan belt
T311
Supply Duct Static Pressure Above Limit
Continue to run unit
Automatic
VFD problem, broken fan belt
T312
Building Static Pressure Below Limit
Continue to run unit
Automatic
Exhaust issues, check setpoint
T313
Building Static Pressure Above Limit
Continue to run unit
Automatic
Exhaust
issues, check setpoint
T314
IAQ Above Limit
Continue to run unit
Automatic
Damper or IAQ control issues
Smoke detector switch or external
A404
Fire Shut Down Emergency
Mode (fire-smoke)
Unit Shutdown
Automatic
switch
A405
Evacuation
Emergency
Mode
Run power exhaust
Automatic
Special fire mode control
A406
Pressurization
Emergency
Mode
Run supply fan
Automatic
Special fire mode control
A407
Smoke Purge Emergency
Mode
Run supply and exhaust fans
Automatic
Special fire mode control
T408
Dirty Air Filter
Continue to run unit
Automatic
Dirty filter, switch setting
A409
Supply Fan Status Failure
Stop unit
Automatic
Fan drive failure
T409
Supply Fan Status Failure
Continue to run unit
Automatic
Fan drive failure, or sensor failure
T414
Loss of Communication
with the Belimo Actuator
Close economizer
Automatic
Calibrate economizer,
economizer
failure, wiring
T414
Belimo Actuator
Direction Error
Close economizer
Automatic
Motor direction switch wrong, wiring
T414
Belimo Actuator
Failure
Attempt to close economizer
Automatic
Motor failure
T414
Belimo Actuator Jammed
Close economizer
Automatic
Obstruction
in damper
T414
Belimo Actuator
Range Error
Close economizer
Automatic
Calibrate economizer
R-W1 Jumper Must Be Installed to Run Heat in Service
T420
Test
No heat
Automatic
Add red wire jumpers
T421
Thermostat
Y2 Input ON without Y1 ON
Assume Y2 is Y1
Automatic
Thermostat
wiring error
T422
Thermostat
W2 Input ON without W1 ON
Assume W2 is W1
Automatic
Thermostat
wiring error
T423
Thermostat
Y and W Inputs ON
Alert
Automatic
Thermostat
issues
T424
Thermostat
G Input OFF on a Call for Cooling
Turn fan on
Automatic
Thermostat
or wiring issues
T500
Current Sensor Board Failure - A1
Stop compressor
A1
Automatic
Faulty board or wiring
T501
Current Sensor Board Failure - A2
Stop compressor
A2
Automatic
Faulty board or wiring
T502
Current Sensor Board Failure - B1
Stop compressor
B1
Automatic
Faulty board or wiring
T503
Current Sensor Board Failure - B2
Stop compressor
B2
Automatic
Faulty board or wiring
A700
Supply Air Temperature
Sensor Failure
Stop staged gas heat
Automatic
Faulty sensor or wiring error
T701
Staged Gas Thermistor
1 Failure
Stop staged gas heat
Automatic
Faulty sensor or wiring error
T702
Staged Gas Thermistor
2 Failure
Stop staged gas heat
Automatic
Faulty sensor or wiring error
T703
Staged Gas Thermistor
3 Failure
Stop staged gas heat
Automatic
Faulty sensor or wiring error
A704
Staged Gas Leaving Air Temp Sum Total Failure
Stop staged gas heat
Automatic
Faulty sensor or wiring error
T705
Limit Switch Thermistor
Failure
Stop staged gas heat
Automatic
Faulty switch or wiring
LEGEND
Axxx-
Alarm
Pxxx-
Pre-Alert
CEM
--
Controls Expansion
module
Txxx
--
Alert
IAQ
--
Indoor Air Quality
TXV
--
Thermostatic
Expansion Valve
OAT
--
Outdoor Air Temperature
VFD
--
Variable Frequency Drive
For 48/50A2,A3,A4,A5
units:
Compressor
internal
overload
protector
is open. Internal
overload protectors
are used in the Copeland compressors
in
all units except size 60 ton units with voltages of 208/230-v,
380-v, and 575-v.
Compressor
external overload
protector
(Kriwan
module)
has activated.
The Copeland
compressors
in size 60 ton
units with voltages
of 208/230-v,
380-v, and 575-v use
external overload protector modules that are mounted in the
compressor
wiring
junction
box.
Temperature
sensors
embedded
in the compressor
motor windings
are the inputs
to the module. The module is powered
with 120 vac from
the units main control box. The module output is a normally
closed contact that is wired in series with the compressor
contactor
coil. In a compressor
motor overload
condition,
the contact opens de-energizing
the compressor
contactor.
Circuit
breaker trip. The compressors
are protected
from
short circuit by a breaker in the control box. On the 020-050
size units there is one breaker per two compressors
and on
the 060 size units there is one breaker per compressor.
Wiring Error. A wiring error might not allow the compres-
sor to start.
To check out alerts 051,052,
055 and 056:
1. Turn on the compressor
in question
using Service Test
mode. If the compressor
does not start, then most likely
the problem
is one of the following:
HPS open, open
internal
protection,
circuit breaker
trip, incorrect
safety
wiring, or incorrect
compressor
wiring.
2. If the compressor
does start verify it is rotating
in the
correct direction.
IMPORTANT:
Prolonged
operation
in the wrong direction
can damage the compressor.
Correct rotation can be veri-
fied by a gage set and looking
for a differential
pressure
rise on start-up.
95