ITEM
DCVC
EC.MN
IAQ.M
AQ.CF
IQ.A.C
IQ.A.F
IQ.LC
IQ.LF
OQ.A.C
AQ.SP
IQ.O.P
DAQ.L
DAQ.H
D.F.OF
D.F.ON
IAQ.R
OAQ.L
OAQ.U
AQ.S.R
IQ.R.L
IQ.R.H
OQ.R.L
OQ.R.H
IAQ.P
IQ.PG
IQ.P.T
IQ.P.L
IQ.P.H
IQ.L.O
Table 84 -- Indoor Air Quality Configuration
EXPANSION
DCV ECONOMIZER
SETPOINTS
Economizer
Min.Position
IAQ Demand Vent Min.Pos.
AIR QUALITY CONFIGS
IAQ Analog Sensor Config
IAQ 4-20 ma Fan Config
IAQ Discrete Input Config
IAQ Disc.In. Fan Config
OAQ 4-20ma Sensor Config
]
RANGE
]
UNITS
O - 100
%
0 - 100
%
0-4
0-2
0-2
0-2
0-2
AIR QUALITY SETPOINTS
IAQ Econo Override Pos.
Dill.Air Quality LoLimit
Diff. Air Quality HiLimit
DAQ PPM Fan Off Setpoint
DAQ PPM Fan On Setpoint
Diff. AQ Responsiveness
OAQ Lockout Value
User Determined OAQ
0-100
0-1000
100-2000
0-2000
0-2000
-5-5
0-2000
0-5000
AIR QUALITY SENSOR RANGE
IAQ Low Reference
IAQ High Reference
OAQ Low Reference
OAQ High Reference
IAQ PRE-OCCUPIED
PURGE
IAQ Purge
IAQ Purge Duration
IAQ Purge LoTemp Min Pos
IAQ Purge HiTemp Min Pos
IAQ Purge OAT Lockout
0-5000
0-5000
0-5000
0-5000
Yes/No
5 - 60
0 - 100
0 - 100
35 - 70
I
CON POINT
I
DEFAULT
I ECONOMIN
IAQMINP
IAQANCFG
IAQANFAN
IAQINCFG
IAQINFAN
OAQANCFG
%
IAQOVPOS
DAQ LOW
DAQ HIGH
DAQFNOFF
DAQFNON
IAQREACT
OAQLOCK
OAQ USER
IAQREFL
IAQREFH
OAQREFL
OAQREFH
rain
I IAQPURGE
IAQPTIME
iF
IAQPLTMP
IAQPHTMP
IAQPNTLO
5
Io
o
o
o
o
o
1oo
1oo
7oo
2oo
4oo
o
o
4oo
o
2000
o
2000
No
15
10
35
5O
Table 85 -- Dehumidification
Configuration
ITEM
DEHU
D.SEL
D.SEN
D.EC.D
D.VCF
D.VRA
D.VHT
D.C.SP
D.RH.S
EXPANSION
DEHUMIDIFICATION
CONFIG.
Dehumidification
Config
Dehumidification
Sensor
Econ disable in DH mode?
Vent Reheat Setpt Select
Vent Reheat RAT offset
Vent Reheat Setpoint
Dehumidify Cool Setpoint
Dehumidify RH Setpoint
Vent Reheat Set Point Select (D. V.CF) -- This configuration
determines
how the vent reheat set point is selected.
• D.V..(T
= 0 -- Reheat
follows
an offset subtracted
from
return air temperature
(D. V.RA).
• D.V..(T
= 1 --
Reheat
follows
a dehumidification
heat
set point (D. V..HT).
Vent Reheat RAT Offset (D. V..RA) --
Set point offset used
only during the vent mode. The air will be reheated
to return-
air temperature
less this offset.
Vent Reheat Set Point (D. V..HT) --
Set point used only dur-
ing the vent mode. The air will be reheated to this set point.
Dehumidify
Cool Set Point (D.C.SP)
--
This
is the dehu-
midification
cooling set point.
Dehumidity
RH Set Point (D.RH.S)
-- This is the dehumidi-
fication relative humidity trip point.
OPERATION
-- Dehumidification
and reheat can only occur
if the unit is equipped with either staged gas or hydronic heat.
Dehumidification
without reheat can be done on any unit but
Configuration--+DEHU--+D.SEL
must be set to 2.
If the machine's
control type is a TSTAT type (Configura-
tion-+UNIT_C
TYP=-3 or 4) and the discrete input selection
for the sensor
is not configured
(D.SEN
not equal to 2),
dehumidification
will be disabled.
If the machine's
control type is a TSTAT type ((bnfigura-
tion--+UNIT4:TYP=-3
or 4) and the economizer
is able to
provide cooling,
a dehumidification
mode may be called out,
but the control will not request mechanical
cooling.
If a 2-stage control type is selected ((bnfiguration--+UNIT
4:
!TP = 4 or 6), then the economizer,
if active, locks out
mechanical
cooling during the Dehumidification
mode.
I
RANGE
I
UNITS I
CCNPOINT
I
DEFAULT
0-2
1-2
Yea/No
i_ 95
dFdeltaFdF
I 10-90
%
I
DHSELECT
?
DHSENSOR
DHECDISA
_es
DHVHTCFG
DHVRAOFF
DHVHT
SP
_
DHCOOLSP
45
DHRELHSP
NOTE:
Configuring
Configuration-+DEHU-+D.SENto
1 or
2 will enable
the CEM
board
along
with the sensor
selected
for
control.
NOTE:
If (bnfiguration--+DEHU--+D.SEL
= 1 or 2, then
staged gas control will be automatically
enabled (Configura-
tion-+HEAT-+HT.CF
will be set to 3).
If a tempering,
unoccupied
or "mechanical
cooling locked
out" HVAC mode is present, dehumidification
will be disabled.
An HVAC Off, Vent or Cool mode must be in effect to launch
either a Reheat or Dehumidification
mode.
If an associated
sensor
responsible
for dehumidification
fails, dehumidification
will not be attempted
(SPRH, RARH).
Initiating
a Reheat or Dehumidification
Mode -- To call out
a Reheat mode in the Vent or the Off HVAC mode, or to call
out a Dehumidification
mode in a Cool HVAC mode, one of
the following conditions
must be true:
The space is occupied
and the humidity
is greater
than
the relative
humidity
trip point (D.RH.S).
The space is occupied
and the discrete humidity
input is
closed.
Dehumidification
and Reheat Control
--
If a dehumidifica-
tion mode
is initiated,
the rooftop
will
attempt
to lower
humidity as follows:
Economizer
Cooling
--
The economizer,
if allowed
to
perform
free cooling,
will have
its control
point
(Run
Status-+VIEW--+EC
C P) set to Configuration---_DEHU
--+D.C.SP
If Configuration--+DEHU-+D.EC.D
is dis-
abled, the economizer
will always
be disabled
during
dehmnidification.
Cooling
-- For all cooling
control
types:
A High Cool
HVAC mode will be requested
internally
to the control to
70