Carrier WEATHERMAKER 48J Started Manual page 40

Single package large rooftop units with comfortlink ti version 5.x controls sizes (020-060)
Table of Contents

Advertisement

temperature
(OAT) r ises a bove 7 5For the highest active cir-
cuitsaturated condensing
temperature
(SCT) r ises above t he
HPSP a nd remains onuntil t hecondition isrepaired regardless
ofthe OAT and SCT values.
Any time the alert o ccurs, astrike i scalled o utontheaffect-
edcompressor.
If three s uccessive
strikes occur the compressor
will belocked o utrequiring a manual reset orpower r eset of
the circuit board. The clearing ofstrikes during c ompressor
op-
eration i sacombination
of3complete cycles or15continuous
minutes ofruntflne operation.
If there a re one ortwostrikes on
thecompressor
andthree short c ycles ( ON-OFF, ON-OFF,
ON-OFF) less t han 15minutes each o ccur, thestrikes are reset
tozero fortheaffected compressor.
If thecompressor
turns o n
and runs for15minutes straight withnocompressor
failure, the
compressor
strikes are cleared.
Additionally, some unitscontain C opeland compressors
equipped withadvanced
scroll temperature
protection (ASTP).
A label l ocated a bove t heterminal boxidentifies Copeland
Scroll c ompressor
models t hatcontain t histechnology. See
Fig.5.Advanced scroll temperature
protection isaform ofin-
ternal discharge temperature
protection that u nloads thescroll
compressor
when theinternal temperature
reaches approxi-
mately 3 00E At thistemperature,
aninternal bi-metal disk
valve opens and causes thescroll elements
toseparate,
which
stops compression.
Suction a nddischarge pressures
balance
while themotor c ontinues torun.The longer thecompressor
runs unloaded,
the longer it must cool b efore t hebi-metal disk
resets. See Fig.6.
Tomanually reset ASTR the compressor
should b estopped
and allowed tocool. If the compressor
isnot s topped, the motor
Fig. 5 -- Advanced Scroll Temperature
Protection Label
120
110
J
too
.-_
-
90
.__ _. 80
_g
50
/
4o
._-J
30
/
20/
to
0
0
10
20
30
40
50
60
70
80
90
Compressor
Unloaded
Run
Time
(Minutes)
*Times are approximate.
NOTE: Various factors, including
high humidity, high ambient tem-
perature, and the presence of a sound blanket will increase cool-
down times.
Fig. 6 -- Recommended
Minimum Cool-Down
Time After Compressor is Stopped*
will run until the motor protector
trips, which
occurs up to
90 minutes
later. Advanced
scroll temperature
protection
will
reset automatically
before
the motor protector
resets, which
may take up to 2 hours.
COMPRESSOR
TIME
GUARDS
-- The control will not al-
low any output relay to come on within 3 seconds of any other
output relay. For outputs connected to the compressors,
the con-
trol will use a Compressor Minimum
OFF Thne of 2 minutes, a
Compressor
Minhnum
ON Thne of 3 minutes and a Minhnum
Delay before turning on another compressor of 10 seconds.
COOL MODE
SELECTION
PROCESS
--
The A Series
(_nfortLink
TM
controls offer three distinct methods by which
it may select a cooling mode.
1. Thermostat
(4:TYP=-3
and 4): The thermostat
does not
depend upon the state of occupancy
and the modes are
called out directly by the discrete inputs from the thermo-
stat (Inputs-cSTAT-cY1
and Y2).
2. Occupied VAV cooling types ((: TYP=-I and 2) are called
out
in the
occupied
period
(Operating
Modes--€
MODE-+
OCC=ON).
3. Unoccupied
VAV cooling
types (4:TYP=-I
and 2) are
called out in the unoccupied period (Operating
Modes--€
MODE--cOCC=OFF).
They
are also used
for space
sensor control types (4:TYP=-5 and 6) in both the occu-
pied and unoccupied
periods.
This section is devoted
to the process
of cooling
mode
determination
for the three types outlined above.
VAV Cool
Mode
Selection
during
the Occupied
Period
(4: TYP = 1,2 and Operating
Modes-cMODE
_OCC
=ON)
-- There is no difference in the selection of a cooling mode for
either VAV-RAT or VAV-SPT in the occupied period. The actual
selection of a cool mode, for both control types, is based upon
the controlling
return-air
temperature
(Temperatures-+AIR.
T
_TRL-+R.TMP).
Typically this is the same as the return air
temperature
thermistor
(Temperatures---)AIR.
T---_RAI) except
when under CCN Linkage.
VAV Occupied
(_ol Mode Evaluation
(_nfiguration
-- There
are VAV occupied cooling offsets under Seq_oints.
ITEM
EXPANSION
RANGE
UNITS
CCNPOINT
DEFAULT
V.C.ON
VAV Occ.
0-25
deltaF
VAVOCON
3.5
Cool On Delta
VC.OF
VAV Occ.
1-25
deltaF
VAVOCOFF
2
Cool Off Delta
(_ol
Mode
Determination
--
If the machine
control type
(Configuration--€
UNIT_:
TYP) = 1 (VAV-RAT) or 2 (VAV-
SPT)
and
the
control
is
occupied
(Operating
Modes
-+MODE-cOCC=ON),
then the unit will not follow the occu-
pied cooling set point (OCSP). Instead, the control will follow
two offsets in the determination
of an occupied
VAV cooling
mode (Setpoints -+V..C.ON and Setpoints--cV.. C OF), applying
them to the low-heat offtrip
point and comparing
the resulting
temperature
to the return-air temperature.
The Setpoints--cV.C.ON
(VAV cool mode on offset) and
Setpoints-cV.C.OF
(VAV cool mode off offset) offsets
are
used in coniunction
with the low heat mode off trip point to
determine
when to bring cooling on and off and in enforcing a
true "vent" mode between heating and cooling. See Fig. 7. The
occupied cooling set point is not used in the determination
of
the cool mode. The occupied
cooling
set point is used for
supply air reset only.
m
m
OHSP _
_
V.C. ON
IV.C.
OF
Fig. 7 -- VAV Occupied
Period Trip Logic
4O