Carrier WEATHERMAKER 48J Started Manual page 31

Single package large rooftop units with comfortlink ti version 5.x controls sizes (020-060)
Table of Contents

Advertisement

THIRD
PARTY CONTROL
Thermostat
E
The method of control would be through
the thermostat inputs:
Y1 = first stage cooling
Y1 and Y2 = first and second stage cooling
Wl = first stage heating
Wl and W2 = first and second stage heating
G = supply fan
Alarm Output
E
The alarm output TB4-7 and 8, will pro-
vide relay closure whenever
the unit is under an alert or alarm
condition.
Remote Switch
_
The remote switch may be configured
for three different functions. Under Configuration
--+UNIT, set
RM. (T" to one of the following:
0 = no remote switch
1 = occupied/unoccupied
switch
2 = start!stop switch
3 = occupancy
ovemde
switch
With RM. CF set to 1, no time schedules
are followed
and
the unit follows the remote switch only in determining
the state
of occupancy.
With RM. CF set to 2, the remote switch can be used to shut
down and disable the unit, while still honoring tflne guards on
compressors.
Time schedules,
internal or external, may be run
simultaneously
with this configuration.
With RM.CF
set to 3, the remote input may override
an
unoccupied
state and force the control to go into occupied
mode. As with the start/stop configuration,
an internal or exter-
nal time schedule may continue to control occupancy
when the
switch is not in effect.
Under (bnfiguration-+SW.LG---_RMI.L,
the remote occu-
pancy switch can be set to either a normally open or normally
closed switch input. Normal is defined as either unoccupied,
start
or "not
currently
overridden,"
respective
to
the RM.CF
configuration.
VFD Control
_
On VFD
equipped
supply
fans, supply
duct static pressure control may be left under unit control or be
externally
controlled.
To control a VFD externally
with a 4 to
20 mA signal, set SRRS
to 4, under the Configuration--+SP
menu. This will set the reset to VFD control. When SRRS
= 4,
the static pressure reset function acts to provide
direct VFD
speed control where 4 mA = 0% speed and 20 mA = 100%
(SRMN
and SRMX
will ovemde).
Note that SRCF
must be
set to 1 (VFD Control) prior to configuring
SRRS
= 4. Failure
to do so could result in damage to ductwork due to overpressur-
ization. In effect, this represents
a speed control signal "pass
through"
under
normal
operating
circumstances.
The
(bnfortLink
controller ovemdes
the third party signal for crit-
ical operation
situations,
most notably smoke and fire control.
Wire the input to the controls expansion
module (CEM) using
TB-11 and 12. An optional CEM board is required.
See Appendix C and the VFD literature supplied with the unit
for VFD configurations
and field wiring connections to the VFD.
Supply Air Reset
--
With the installation
of the CEM,
the (_mfortLink
controller
is capable
of accepting
a 4 to
20 mA signal, to reset the supply-air temperature
up to a maxi-
mum of 20 E See VFD Control section above.
Demand
Limit Control _
The
term
"demand
limit
control" refers to the restriction
of the machine's
mechanical
cooling capacity to control the amount of power that a machine
may use.
Demand limiting using mechanical
control is possible
via two
means:
Two discrete inputs tied to demand lhnit set point percentages.
OR
A 4 to 20 mA input that can reduce or limit capacity linearly to
a set point percentage.
In either case, it will be necessary to install a controls ex-
pansion module (CEM).
DEMAND LIMIT DISCRETE INPUTS -- First, set DM.L.S
in (bnfiguration-+DMD.L
to 1 (2 switches).
When Inputs-cGEN.I-cDL.S1
(Demand Switch no. 1) is
OFF, the control will not set any limit to the capacity, and
when ON, the control sets a capacity limit to the Configura-
tion--cDMD.L -¢D.L.S1 set point.
Likewise, when Inputs-cGEN.I-cDL.S2
(Demand Switch
no. 2) is OFF, the control will not set any limit to the capacity,
and when ON, the control sets a capacity lflnit to the Configu-
ration--cDMD.L--cD.L.S2 set point.
If both switches are ON, Inputs-cGEN.I-cDL.S2
is used
as the limiter of capacity.
Under (bnfiguration--cSW..LG
set the logic state appropri-
ately for the action desired. Set the DL1.L and DL2.L configu-
rations. They can be set normally open or normally closed. For
example, ifDL1.L is set to OPEN, the user will need to close
the switch to cause the control to limit capacity to the demand
limit 1 set point. Likewise, if DL1.L is set to CLSE (closed),
the user will need to open the switch to cause the control to
limit capacity to the demand limit 1 set point.
DEMAND LIMIT 4 TO 20 mA INPUT -- Under (bnfigu-
ration--cDMD.L,
set configuration DM.L.S to 2 (2 = 4 to
20 mA control). Under the same menu, set D.L.20 to a value
from 0 to 100% to set the demand lflnit range. For example,
with D.L.20 set to 50, a 4 mA signal will result in no limit to
the capacity and 20 mA signal will result in a 50% reduction in
capacity.
Demand
Controlled
Ventilation
Control
There are multiple methods for externally
controlling the econ-
omizer damper.
IAQ DISCRETE
1NPUT CONFIGURATION--
The IAQ dis-
crete input configuration
requires a CEM module (optional)
to
be installed and an interface to a switch input at TB5-6 and 7.
The
state of the input
on the display
can be
found
at
Inputs --)AIR. Q--+IA Q.I.
Before configuring
the switch functionality,
first determine
how the switch will be read. A closed switch can indicate either
a low IAQ condition
or a high IAQ condition.
This is set at
Configuration-+SW.LG
and IAQ.L.
The user can set what a
low reading would mean based on the type of switch being
used. Setting IAQ.L
to OPEN means that when the switch is
open the input will read LOW. When the switch is closed, the
input will read HIGH. Setting IAQ.L to CLSE (closed) means
that when the switch is closed the input will read LOW, and
therefore, when the switch is open the switch will read HIGH.
There are two possible
configurations
for the IAQ discrete
input.
Select
item
(bnfiguration--clAQ--)AQ.CF--clQ.LC
and configure
for either 1 (IAQ Discrete)
or 2 (IAQ Discrete
Override).
IQ.L C = 1 (IAQ Discrete)
-- If the user sets IQ.L C to 1 (IAQ
Discrete),
and the switch
logic
((bnfiguration--cSW.LG--€
IAQ.L)
is set to OPEN, then an open switch reads low and a
closed switch reads high.
If the switch is open, the economizer
will be colmnanded
to
the IAQ Demand Vent Minimum
Position.
These settings may be adjusted and are located at (bnfigura-
tion --+IAQ--+DC V.C-+IA Q.M.
If the switch is closed, the IAQ reading will be high and the
economizer
will be colmnanded
to the Economizer
Minimum
Position.
This setting may be adjusted
and is located
at Configura-
tion --dA Q --cDC V.C-cE C MN.
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents