Table 39 -- Motor Limitations
HIGH-EFFICIENCY
MOTORS
Nominal
Maximum
Maximum Amps
Maximum
Maximum
Bhp
BkW
Bhp
BkW
230 v
460 v
575 v
Watts
Efficiency
5
3.73
5.9
4.40
15.0
7.9
6.0
5,030
87.5
8.7
6.49
23.5
--
--
7,717
84.1
7.5
5.6
9.5
7.09
--
12.0
10.0
8,008
88.5
10.2
7.61
31.0
--
--
9,502
89.5
10
7.46
11.8
8.80
--
15.0
12.0
9,836
89.5
15.3
11.41
46.0
--
--
12,543
91.0
15
11.19
18.0
13.43
--
22.0
19.0
14,756
91.0
22.4
16.71
60.0
--
--
18,363
91.0
20
14.92
23.4
17.46
--
28.7
23.0
19,183
91.0
28.9
21.56
73.0
--
--
23,511
91.7
25
18.65
29.4
21.93
--
37.4
28.4
23,918
91.7
35.6
26.56
91.0
--
--
28,742
92.4
30
22.38
34.7
25.89
--
43.8
36.3
28,015
92.4
40
29.84
42.0
31.33
110.0
55.0
43.8
33,690
93.0
PREMIUM-EFFICIENCY
MOTORS
Nominal
Bhp
5
7.5
10
15
20
25
30
40
BkW
3.73
5.6
7.46
11.19
14.92
18.65
22.38
29.84
Bhp
5.9
8.7
9.5
10.2
11.8
15.3
18.0
22.4
23.4
28.9
29.4
35.6
34.7
42.0
Maximum
BkW
4.40
6.49
7.09
7.61
8.80
11.41
13.43
16.71
17.46
21.56
21.93
26.56
25.89
31.33
LEGEND
--
Brake Horsepower
--
Brake Kilowatts
Maximum
Amps
230 v
460 v
15.8
7.9
23.5
--
12.0
30.0
--
15.0
46.0
--
22.0
59.0
--
28.7
73.0
--
36.3
82.6
--
41.7
110.0
55.0
Maximum
Watts
4,918
7,078
7,728
8,298
9,600
12,273
14,439
17,853
18,650
23,034
23,432
28,374
27,656
33,156
Maximum
Efficiency
89.5
91.7
91.7
91.0
91.7
91.7
93.0
93.0
93.6
93.6
93.6
93.6
93.6
94.5
Bhp
BkW
NOTES:
1. Extensive
motor and electrical
testing on the Carrier units has ensured that
the full horsepower
range of the motor can be utilized with confidence.
Using the fan motors up to the horsepower
ratings shown in the Motor Lim-
itations table will not result in nuisance tripping
or premature
motor fail-
ures. Unit warranty will not be affected.
2. All motors comply
with Energy
Policy Act (EPACT)
Standards
effective
October 24, 1997.
Table 40A -- Air Quantity Limits (48AJ,AK,AW,AY,A2,A3,A4,A5)
MAXIMUM AIRFLOW
UNIT SIZE*
CFM
020
025
027
030
035 (AJ,AK,AW,AY)
035(A2,A3,A4,A5)
036,040,041
050
051,060
LEGEND
CV
--
Constant Volume
VAV
--
Variable Air Volume
MINIMUM HEATING
AIRFLOW CFM
(Low Heat)
5,900
5,900
5,900
5,900
5,900
5,900
7,600
7,600
11,000
MINIMUM HEATING
AIRFLOW CFM
(High Heat)
6,100
6,100
6,100
6,100
6,100
10,100
10,100
10,100
10,100
MINIMUM COOLING
AIRFLOW (VAV) CFM
AT FULL LOAD
4,000
5,000
5,400
6,000
7,000
7,000
8,000
10,000
12,000
MINIMUM COOLING
AIRFLOW
CFM
(CV)
6,000
7,500
8,100
9,000
10,500
10,500
12,000
15,000
18,000
* Sizes 036,041,
and 051 are 48AJ,AK,AW, AY only.
10,000
12,500
13,500
15,000
17,500
17,500
20,000
22,500
27,000
NOTE: Variable air volume units will operate
down to 70 cfm/ton
in Cooling
mode. Performance
at 70 cfm/ton is limited to unloaded
operation and may be
also limited by edb (entering dry bulb) and ewb (entering wet bulb) conditions.